7 dimensions, 6 scadapack, Wiring plan – VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual
Page 81: Parameter
81
10 Supplement
VEGAPULS 62 • Modbus and Levelmaster protocol
41362-EN-121011
10.6 ScadaPack
Wiring plan
+
+
power supply
MODBUS
D0
D1
IS GND
USB
1
3
2
13
45
5
2
1
3
4
9
6
7
8
2o
ff
on
( )
(
)
(-)
(-)
+8
+30 Vdc
to
GND
COM Part 3 (C3)
RS485
TXD-
TXD+
GND
Fig. 59: Connection of VEGAPULS 62 to RTU ScadaPack
1 VEGAPULS 62
2 RTU ScadaPack
3 Voltage supply
Parameter
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
Floating Point
Input Register Base Number
30001
The basic number of the input registers is always added to the input register address of VEGAPULS
62.
Address 31303 must hence be entered as register address for 1302 for RTU ScadaPack.
10.7 Dimensions
The following dimensional drawings represent only an extract of the possible versions. Detailed
dimensional drawings can be downloaded at www.vega.com/downloads under "Drawings".