2 basics modbus, 2 bus description, 2 bus architecture – VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual

Page 66: 2 basics modbus 10.2 bus description

Advertising
background image

66

10 Supplement

VEGAPULS 62 • Modbus and Levelmaster protocol

41362-EN-121011

Ʋ Inspection window

Polyester foil

Integrated clock
Date format

Day.Month.Year

Time format

12 h/24 h

Time zone Ex factory

CET

Measurement electronics temerature
Resolution

1 °C (1.8 °F)

Accuracy

±1 °C (1.8 °F)

Voltage supply
Operating voltage

8 … 30 V DC

Interpolation protection

Available

Electrical protective measures
Protection, depending on housing version

Ʋ Plastic housing

IP 66/IP 67

Ʋ Aluminium housing, stainless steel

housing - investment casting, stain-

less steel housing - electro-polished

IP 66/IP 68 (0.2 bar)

6)

Ʋ Aluminium and stainless housing, in-

vestment casting (optionally available)

IP 66/IP 68 (1 bar)

Overvoltage category

III

Protection class

III

Approvals
Instruments with approvals can have different technical data depending on the version.
For that reason the associated approval documents of these instruments must be carefully noted.

They are part of the delivery or can be downloaded under www.vega.com and "VEGA Tools" as

well as under "Downloads" and "Approvals".

10.2 Basics Modbus

10.2 Bus description

The Modbus protocol is a communication protocol for the communication between instruments. It is

based on a Master/Slave or Client/Server architecture. By means of Modbus, a Master and several

Slaves can be connected. Each bus participant has an unambiguous address and can send mes-

sages to the bus. This is initiated by the Master, the addessed Slave answers. The versions Ethernet

and serial (EIA-232 and EIA-485) as well as the modes ASCII, TCP and RTU are available for the

data transfer. In the RTU and ASCII mode interesting here, data will be transmitted in binary form.

The telegram consists generally of the address, the function, the data as well as the transmission

check.

10.2 Bus architecture

In the version Modbus RTU, up to 32 participants can be connected to the bus. The length of the

6)

The prerequisites for maintaining the protection rating are a suitable cable as well as correct mounting.