10 Supplement

VEGAPULS 62 • Modbus and Levelmaster protocol

41362-EN-121011

10.6 ABB Total Flow

Wiring plan

+

+

power supply

MODBUS

D0

D1

IS GND

USB

1

2

13

45

2o

ff

on

( )

(

)

(-)

(-)

8

1

2

6

7

Bus +

Bus -

GND

VBAT

Fig. 56: Connection of VEGAPULS 62 to RTU ABB Total Flow
1 VEGAPULS 62

2 RTU ABB Total Flow

Parameter

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

16 Bit Modicon

Input Register Base Number

1

The basic number of the input registers is always added to the input register address of VEGAPULS

62.
Address 1303 must hence be entered as register address for 1302 for RTU ABB Total Flow.