Dexter Laundry T-1450 EXPRESS (30-Cycle) User Manual

Page 16

Advertising
background image

16

Step 12 - Intermediate spin.

The I/O interface outputs labeled Reverse and Speed1 will be active

(the two RED LED’s will light).

Step 13 - Full speed spin.

The I/O interface outputs labeled Reverse, Speed1 and Speed2 will be

active (the three RED LED’s will light).


DO NOT USE STEP 14 IF YOU HAVE CUSTOMIZED CYCLES PROGRAMMED, AS
THIS WILL SET THE CYCLES BACK TO THE FACTORY PRESETS.

Step 14 - Preset Cycles. Push START and hold, then push SCROLL UP. This

will reset the DEXTER preset cycles back to the factory settings.

At cycle complete, switch the Advance/Run/Program switch to the Run position,

and the unit is ready to select a run cycle.

RAPID ADVANCE MODE

To enter the Rapid Advance mode, insert the key into the Rapid

Advance/Run/Program lock and turn the key counter-clockwise (CCW). The Rapid

Advance mode must be entered during the cycle. If the cycle has not yet

started, press the “DOWN” button or the “UP” button to choose a cycle and then

the “START” button to begin the cycle.

To advance to the next step in the cycle, push both the “UP” and “START”

buttons at the same time. The display will show “Ad” (advance).

If advancing during a bath, all water valves will turn off and the drain will

open until the “open drain” step is completed. The cycle will then continue to

the next bath or to the spin of the current bath if the programming includes

spin time.

If advancing during a chemical injection of a bath or after a chemical

injection of the bath but before the low water level is reached, the injector

will turn off and the hot and the cold water valves to the tub will turn on

until the low water level is reached or for 30 seconds, whichever comes first.

Then the drain will open and proceed to the next step after the “open drain”

step is completed.

If advancing before a chemical injection of the bath, the drain will open

immediately and the cycle will proceed to the next step when the “open drain”

step is completed.

If advancing during a spin, the tumbler will begin to decelerate immediately.

However the cycle may proceed to the next bath before the tumbler comes to a

complete stop. The cycle cannot be advanced further while the tumbler is

decelerating.

If a temperature PCB is installed in the I/O PCB and the temperature programmed

from 20 to 90 (Celsius), advancing will turn off the heater relay or steam

valve immediately, if either is on, and open the drain after a three second

delay. If the display shows a water temperature from 65 to 90 (may be

displayed by pressing the “DOWN” and “START” buttons together), the drain will

close again when the washer indicates empty and the hot and the cold water

valves to the tub will turn on until the low water level is reached. The cycle

will then continue to the next bath, or if programmed, to the spin of the

current bath.

To exit the Rapid Advance mode during the cycle, turn the key to Run. The

cycle will continue normally.