ELECTRICAL

╔════════════════════════════════════════════════════════════════════╗

WARNING
SHUT OFF POWER AND WATER BEFORE OPENING ANY SERVICE PANELS.

╚════════════════════════════════════════════════════════════════════╝

Dexter T1450 washing machines are intended to be permanently installed

appliances. The machine should be connected to an individual branch circuit

not shared by lighting or other equipment. The connection should be sheathed

in liquid-tight flexible conduit, or equivalent, with conductors of the proper

size and insulation. No power cord is provided. Such connections should be

made by a qualified electrician, in accordance with the wiring diagram.

FUSING REQUIREMENTS

30 Amp Time Delay (Dual Element) Fuse(s) (or equivalent circuit breaker).

TO MAKE ELECTRICAL CONNECTIONS:

Remove screw and lift out cover located on upper left of machine (viewed from

back).

Figure 3 - Electrical Power Connections. 208-240 VAC, 1 or 3 Phase, 60 Hertz

If power is 208-240-3PH-60HZ

connect L1, L2, L3 and ground.

(If there is a high phase it

must be connected to L3.)

If power is 208-240-1PH-60HZ

connect L1, L2 and ground.

IMPORTANT


FOR SAFETY AND PROPER EQUIPMENT
OPERATION THE

GROUND LUG MUST BE

CONNECTED TO A GOOD EXTERNAL
GROUND.