5 network connection – GE Industrial Solutions AF-600 FP Apogee_FLN User Manual
Page 18
5 Network Connection
5.1.1 Network Connection
Connect the frequency converter to the RS-485 network as follows (see also diagram):
1.
Connect signal wires to terminal 68 (P+) and terminal 69 (N-) on the main control board of the frequency converter.
2.
Connect the cable screen to the cable clamps.
NB!
Screened, twisted-pair cables are recommended in order to reduce noise
between conductors.
Illustration 5.1: Network Terminal Connection
130BB018.10
Illustration 5.2: Control card terminals
5.1.2 Frequency Converter Hardware Setup
Use the terminator dip switch on the main control board of the frequency
converter to terminate the RS-485 bus.
Terminator Switch Factory Setting
NB!
The factory setting for the dip switch is OFF.
5.1.3 Electrical installation
NB!
Electrical installation: Please see AF-600 FP Operating Instructions.
AF-600 FP Apogee FLN Operating Instructions
17
5