5 Network Connection

5.1.1 Network Connection

Connect the frequency converter to the RS-485 network as follows (see also diagram):

1.

Connect signal wires to terminal 68 (P+) and terminal 69 (N-) on the main control board of the frequency converter.

2.

Connect the cable screen to the cable clamps.

NB!
Screened, twisted-pair cables are recommended in order to reduce noise
between conductors.

Illustration 5.1: Network Terminal Connection

130BB018.10

Illustration 5.2: Control card terminals

5.1.2 Frequency Converter Hardware Setup

Use the terminator dip switch on the main control board of the frequency
converter to terminate the RS-485 bus.

Terminator Switch Factory Setting

NB!
The factory setting for the dip switch is OFF.

5.1.3 Electrical installation

NB!
Electrical installation: Please see AF-600 FP Operating Instructions.

AF-600 FP Apogee FLN Operating Instructions