6 Parameters

6.1.1 Parameter Settings

The frequency converter has a unique FLN address, which is transmitted over the RS-485 serial bus. The network will recognize the Drive, which may then be
programmed for setup options. The parameters listed in the table below need to be set for each Drive on the FLN network. FLN communication related parameters
can only be set by using the Keypad.

NB!
As a minimum, it is required to set par. O-30 Protocol to FLN; par. O-31 Address, to the proper address and par. O-32 Drive Port Baud Rate to the proper baud
rate. (See AF-600 FP Programming Guide).

par. O-50 Coasting Select through par. O-56 Preset Reference Select are options that select control of the drive through the digital and/or the FLN serial port.

Parameter

Default

Desired setting

*par. O-03 Control Word Timeout Time

0

*par. O-04 Control Word Timeout Function

0ff

*par. O-30 Protocol

Drive

FLN

*par. O-31 Address

1 through 98

*par. O-32 Drive Port Baud Rate

9600

4800 or 9600

**par. O-50 Coasting Select

Logic or

**par. O-52 DC Brake Select

Logic or

**par. O-53 Start Select

Logic or

**par. O-54 Reversing Select

Digital input

**par. O-55 Set-up Select

Logic or

**par. O-56 Preset Reference Select

Logic or

Table 6.1: Frequency converter parameter settings

* Minimum parameters, which must be set to operate the frequency converter via the FLN serial interface.
** When [Digital input] or [Logic or] is selected, digital inputs may interfere with serial bus commands. The setting [Serial communication] allows serial bus
commands to be carried out only. See the AF-600 FP Programming Guide for detailed descriptions.

NB!
The frequency converter can store preset references programmed in parameters

C-05.0 through C-05.7, Multi-Step Frequency (1-8). To avoid these values

modifying serial bus references, set par. F-54 Reference Function to [External/Preset]. See AF-600 FP Programming Guide for detailed descriptions.

AF-600 FP Apogee FLN Operating Instructions