7.3 Start-up

7.3.1 Start-up of FLN Control

This procedure assumes that the frequency converter has been installed properly and is operational in Hand control mode. It also assumes the Siemens FLN data
bus is connected to an operational controller. Start the Drive in accordance with the following procedure.

1.

Ensure that the assumptions in this procedure are correct.

2.

Check that the network connections are securely fastened in accordance with Figure Network Terminal Connection

Verify compliance with all safety requirements listed in this manual.

3.

Apply power to the frequency converter.

4.

Ensure that the minimum settings listed in Table Drive Parameter Settings are selected.

5.

Ensure that the switch positions in Figure Drive Terminator Switch Factory Settingare set correctly.

6.

Optional settings may be changed to meet or enhance frequency converter operation, depending on the application requirements.

7.

For FLN control of the drive, press the A

uto key on the Keypad. Drive operation can then be controlled through the host network device in

accordance with its operation instructions.

NB!
Default setting for point number 35, Run Enable, is [OFF]. Drive will not operate until Run Enable [ON] signal is given through serial communication network.

AF-600 FP Apogee FLN Operating Instructions