Af-600 fp apogee fln operating instructions – GE Industrial Solutions AF-600 FP Apogee_FLN User Manual

Page 24

Advertising
background image

No.

Description

Warning

Alarm/Trip

Alarm/Trip Lock

Parameter Reference

1

10 Volts low

X

2

Live zero error

(X)

(X)

par. AN-01 Live Zero Time-

out Function

3

No motor

(X)

par. H-80 Function at Stop

4

Mains phase loss

(X)

(X)

(X)

par. SP-12 Function at Line

Imbalance

5

DC link voltage high

X

6

DC link voltage low

X

7

DC over voltage

X

X

8

DC under voltage

X

X

9

Inverter overloaded

X

X

10

Motor Electronic Overload over temperature

(X)

(X)

par. F-10 Electronic Over-

load

11

Motor thermistor over temperature

(X)

(X)

par. F-10 Electronic Over-

load

12

Torque limit

X

X

13

Over Current

X

X

X

14

Earth fault

X

X

X

15

Incomp. HW

X

X

16

Short Circuit

X

X

17

Control word timeout

(X)

(X)

par. O-04 Control Word

Timeout Function

23

Internal fans

24

External fans

25

Brake resistor short-circuited

X

26

Brake resistor power limit

(X)

(X)

par. B-13 Braking Thermal

Overload

27

Brake chopper short-circuited

X

X

28

Brake check

(X)

(X)

par. B-15 Brake Check

29

Power board over temp

X

X

X

30

Motor phase U missing

(X)

(X)

(X)

par. H-78 Missing Motor

Phase Function

31

Motor phase V missing

(X)

(X)

(X)

par. H-78 Missing Motor

Phase Function

32

Motor phase W missing

(X)

(X)

(X)

par. H-78 Missing Motor

Phase Function

33

Inrush fault

X

X

34

Network communication fault

X

X

36

Mains failure

38

Internal fault

X

X

40

Overload T27

41

Overload T29

42

Overload X30/6-7

47

24 V supply low

X

X

X

48

1.8 V supply low

X

X

49

Speed limit

50

Auto Tune calibration failed

X

51

Auto Tune check U

nom

and I

nom

X

52

Auto Tune low I

nom

X

53

Auto Tune motor too big

X

54

Auto Tune motor too small

X

55

Auto Tune parameter out of range

X

56

Auto Tune interrupted by user

X

57

Auto Tune timeout

X

58

Auto Tune internal fault

X

X

59

Current limit

X

60

External interlock

62

Output Frequency at Maximum Limit

X

64

Voltage Limit

X

65

Control Board Over-temperature

X

X

X

66

Heat sink Temperature Low

X

67

Option Configuration has Changed

X

70

Illegal Drive configuration

80

Drive Initialised to Default Value

X

92

No-Flow

X

X

Par. AP-2#

93

Dry Pump

X

X

Par. AP-2#

94

End of Curve

X

X

Par. AP-5#

95

Broken Belt

X

X

Par. AP-6#

96

Start Delayed

X

Par. AP-7#

97

Stop Delayed

X

Par. AP-7#

98

Clock Fault

X

K-7#

Table 7.1: Alarm/Warning code list