1.2.1 Introduction

The Siemens Floor Level Network (FLN) is a master/ slave control network for serial communication with various control devices. The FLN controller is RS-485
compatible, half duplex, with an operating rate of 4800 or 9600 baud. Recommended wiring is shielded, twisted pair. The FLN software protocol is designed to be
general in nature to accommodate any unique properties of each device type. The node address system allows up to 96 devices to be used on any one system.

The GE drive is a programmable frequency converter, which controls the operation of 3-phase, standard induction electrical motors in the HVAC industry. The
drive control card has FLN communication protocol software built-in. The drive uses optical isolation for fault tolerance and noise immunity.

The FLN communicates directly with the drive drive via the RS-485 serial interface bus. In addition to being able to control the drive, most drive configuration and
control parameters can be reviewed and changed through the FLN. Also, the operational status of the drive can be read and monitored through the bus. Diagnostic
and operational information stored in the drive is easily available, such as kWh of energy used, total operation hours, drive status, motor speed, and many other
useful items which can be accessed and monitored through the FLN.

The FLN is designed to communicate with any controller node that supports the interfaces defined in this document.

1.2.2 About this Manual

The documentation in this manual provides comprehensive information on the connection, programming, and startup of the drive for use with the FLN. It is
intended as both an instruction and reference manual. Functions and features of the drive frequency converter are also briefly reviewed to serve as a guideline
to optimize your communication system. Read this manual before programming since important information is provided in each section. For detailed information
on using the drive, see the Operating Instructions.

1.2.3 Assumptions

This manual assumes that the controller node supports the interfaces in this document and that all the requirements and limitations stipulated in the controller
node and the drive are strictly observed. It is assumed that the user understands the general capabilities and limitation of the controller node and the drive
Frequency Converter.

1.2.4 Available literature for AF-600 FP

-

Operating Instructions provide the necessary information for getting the drive up and running.

-

Design Guide entails all technical information about the drive and customer design and applications.

-

Programming Guide provides information on how to program and includes complete parameter descriptions.

GE technical literature is available in print from your local GE Sales Office or online at: www.geelectrical.com/drives
- AF-600 FP Built-in network manuals are available separately.

AF-600 FP Apogee FLN Operating Instructions