No.

Description

Warning

Alarm/Trip

Alarm/Trip Lock

Parameter Reference

200

Fire Mode

X

FB-0#

201

Fire Mode was Active

X

K-7#

202

Fire Mode Limits Exceeded

X

K-7#

250

New spare part

251

New model number

Table 7.2: Alarm/Warning code list, continued..

(X) Dependent on parameter

LED indication

Warning

yellow

Alarm

flashing red

Trip locked

yellow and red

Alarm Word and Extended Status Word
Bit

Hex

Dec

Alarm Word

Warning Word

Extended Status Word

0

00000001

1

Brake Check

Brake Check

Ramping

1

00000002

2

Pwr. Card Temp

Pwr. Card Temp

Auto Tune Running

2

00000004

4

Earth Fault

Earth Fault

Start CW/CCW

3

00000008

8

Ctrl.Card Temp

Ctrl.Card Temp

Slow Down

4

00000010

16

Ctrl. Word TO

Ctrl. Word TO

Catch Up

5

00000020

32

Over Current

Over Current

Feedback High

6

00000040

64

Torque Limit

Torque Limit

Feedback Low

7

00000080

128

Motor Th Over

Motor Th Over

Output Current High

8

00000100

256

Motor Electronic Overload
Over

Motor Electronic Overload Over

Output Current Low

9

00000200

512

Inverter Overld.

Inverter Overld.

Output Freq High

10

00000400

1024

DC under Volt

DC under Volt

Output Freq Low

11

00000800

2048

DC over Volt

DC over Volt

Brake Check OK

12

00001000

4096

Short Circuit

DC Voltage Low

Braking Max

13

00002000

8192

Inrush Fault

DC Voltage High

Braking

14

00004000

16384

Mains ph. Loss

Mains ph. Loss

Out of Speed Range

15

00008000

32768

Auto Tune Not OK

No Motor

OVC Active

16

00010000

65536

Live Zero Error

Live Zero Error

17

00020000

131072

Internal Fault

10V Low

18

00040000

262144

Brake Overload

Brake Overload

19

00080000

524288

U phase Loss

Brake Resistor

20

00100000

1048576

V phase Loss

Brake IGBT

21

00200000

2097152

W phase Loss

Speed Limit

22

00400000

4194304

Network Fault

Network Fault

23

00800000

8388608

24 V Supply Low

24V Supply Low

24

01000000

16777216

Mains Failure

Mains Failure

25

02000000

33554432

1.8V Supply Low

Current Limit

26

04000000

67108864

Brake Resistor

Low Temp

27

08000000

134217728

Brake IGBT

Voltage Limit

28

10000000

268435456

Option Change

Unused

29

20000000

536870912

Drive Initialised

Unused

30

40000000

1073741824

Safe Stop

Unused

Table 7.3: Description of Alarm Word, Warning Word and Extended Status Word

The alarm words, warning words and extended status words can be read out via serial bus or optional field-bus for diagnosis. See also par. DR-90 Alarm Word,
par. DR-92 Warning Word and par. DR-94 Ext. Status Word.

AF-600 FP Apogee FLN Operating Instructions

24

7

Advertising