1.6.1.4 User-Defined Overcurrent Protection test
Provides operators with a more advanced method for Overcurrent Protection testing. Operators
set the Pre-Fault, Fault, and Post-Fault levels for the circuit breaker under test.
Figure 1-13 User-Defined Overcurrent Protection test
Quick Test Guide
1. Enter Operator Name and Test Description.
2. Select a Breaker.
3. Select Breaker Trip or No Trip Test.
4. Select Ground Fault Defeat or Resume depending on Fault Phase(s) desired.
5. Set the required fault levels.
a. Select Level (Pre-Fault, Fault, or Post-Fault).
b. Set the % of CT & Phase Angle for Phase IA, IB, IC, and Neutral.
c. Repeat for each Level.
6. Set the Pre-Fault, Fault, and Post-Fault times.
7. Click Apply to save the test parameters.
8. Click Perform Test.