GE Industrial Solutions Entellisys System Test Kit User Manual

Page 39

Advertising
background image

System Test Kit

40

Table 1-14 Default values for user-defined relay protection tests

User-Defined

Frequency / Multiplier / KW Range

Prefault

Fault

Post Fault

Over Frequency

50 Hz – 60 Hz
0.1 Hz increment

50 Hz – 70 Hz
0.1 Hz increment

50 Hz – 60 Hz
0.1 Hz increment

Under Frequency

50 Hz – 60 Hz
0.1 Hz increment

44 Hz – 60 Hz
0.1 Hz increment

50 Hz – 60 Hz
0.1 Hz increment

Overvoltage

96% to 104%
0.5% increment

104% to 132%
0.5% increment

96% to 104%
0.5% increment

Undervoltage

96% to 104%
0.5% increment

47.5% to 95%
0.5% increment

96% to 104%
0.5% increment

Phase Loss

0% to 7%
1% increment

7% to 51%
1% increment

0% to 7%
1% increment

Power Reversal

0 to 100 KW
10 KW increment

0 to 1000 KW
10 KW increment

0 to 100 KW
10 KW increment

High Current

0% to 100%
5% increment

45% to 205%
5% increment

0% to 100%
5% increment