3 relay protection test results screen – GE Industrial Solutions Entellisys System Test Kit User Manual
Page 40
Test Menu
41
1.6.2.3 Relay Protection Test Results screen
The Relay Protection Test Results screen will display the results for the tests performed using
the user-defined tests.
Figure 1-19 Relay protection test results screen
Test settings and results are saved to the hard-drive with the report name as TestNumber_Time.
Table 1-15 Selections and controls
Level
Select the fault level to display the test settings.
User-Defined Test Settings
Summarizes the test performed at the level shown.
Test Results
Once the test is performed, it displays the time sequence of circuit breaker
status and the device that actuated the circuit breaker (Shunt Trip or Flux
Shifter).
Expected Trip Time
Expected trip time automatically calculated from the pickup, delay band
settings, and beaker clearing time.
Observed Trip Time
Observed trip time displayed after the test is performed.
Test Summary LED
Specifies the test results by comparing the observed trip time with the
expected trip time.
Green
Successful (within +/– 20% of expected time)
Red
Unsuccessful
Gray
Test Aborted