2 manual circuit breaker injection input range – GE Industrial Solutions Entellisys System Test Kit User Manual
Page 46
Manual Breaker Injection
47
1.9.2 Manual circuit breaker injection input range
Frequency
Frequency of the Signal to be injected.
Breaker Connection
Flow current Forward / Reverse connected circuit breakers.
Voltage Inputs
Inputs for Voltage Phases.
Current Inputs
Inputs for Current phases.
Test Settings for Fault Generation
Display of Current and Voltage settings.
Test Results
Once the test is performed, it displays the time stamping of circuit
breaker status and the device that actuated the circuit breaker (Flux
Shifter or Breaker Open).
Test Time
Time entry for test kit execution.
Table 1-16 Setup
Table 1-17 Manual circuit breaker injection input range
Parameter
Range
Voltage
0 to 2x PT Rating Volts
Current
0 to 28x CT Rating Amps
Phase Angle
–360° to +360°
Test Time
0.5 to 17000 secs