SECTION 4 INSTALLING THE

CONVERSION

KIT

(CONTINUED)

Wire Harness Connector Assembly and
Installation


The wire harness includes a 36-pin programmer connector,
which must be assembled and installed to the programmer
bracket prior to the installation of the programmer unit.

WARNING: THE ADAPTER BRACKET MUST BE
INSTALLED ONTO THE PROGRAMMER 36-PIN
CONNECTOR AND PROGRAMMER BRACKET AS
DETAILED BELOW. FAILURE TO DO SO WILL
RESULT IN HARNESS PLUG FAILURE AND THE
PROGRAMMER WILL NOT PROVIDE
PROTECTION. IF THE CONVERTED BREAKER IS
ENERGIZED OR PRIMARY INJECTED WITH THE

10

ADAPTER BRACKET NOT INSTALLED OR
INSTALLED IMPROPERLY, DAMAGE WILL
RESULT TO THE PROGRAMMER UNIT, WIRE
HARNESS, 36-PIN CONNECTOR, AND CT’S.
FAILURE TO ADHERE TO THESE INSTRUCTIONS
WILL VOID ALL WARRANTIES.

Step 1.

Slide the adapter bracket onto the 36-pin programmer
connector (Figs. 16a & 16b). Be sure that the beveled
corners of the programmer connector are facing toward the
right side, the adapter bracket slides in place behind the
notches on either side of the connector body, and that the
connector’s tabs align with the notches provided on the
bottom of the adapter bracket.

Step 2.

Hold the adapter bracket tight to the programmer connector
and bend the two (2) locking tabs provided on the adapter
bracket over the connector body (Fig. 16c).

Fig. 16a. 36-Pin Programmer Connector

Fig. 16b. Adapter Bracket

Fig. 16c. Adapter Bracket Locking Tabs