GE Industrial Solutions MicroVersaTrip Plus and MicroVersaTrip PM DS-206, DSL-206,DS-416, DSL-416, DS-420, DS-632 User Manual

Page 8

Advertising
background image

SECTION 4 INSTALLING THE

CONVERSION

KIT

(CONTINUED)

Flux Shifter Assembly, Adjustment and
Installation


The new MicroVersaTrip

®

flux shifter will be supplied

from the factory with the actuator shaft and shoe
assembled. Prior to installation, the actuator shaft and shoe
components must be disassembled from the flux shifter and
then reassembled into the Westinghouse

®

actuator frame

along with the flux shifter device.

Step 1.

Remove and retain the two (2) jamb hex nuts used to attach
the shoe to the actuator shaft of the flux shifter (Fig. 12 &
13). Slide the actuator shaft out of the flux shifter
assembly. Save all hardware.

Step 2.

Install the flux shifter assembly onto the Westinghouse

®

actuator frame using the two (2) #10 hex nuts and lock
washers provided (Fig. 14).

Fig. 12. Flux Shifter Assembly

as Shipped from Factory

Fig. 13. Actuator Shaft and Shoe Removal

Fig. 14. Flux Shifter Mounting


8

Advertising