GE Industrial Solutions MicroVersaTrip Plus and MicroVersaTrip PM DS-206, DSL-206,DS-416, DSL-416, DS-420, DS-632 User Manual

Page 13

Advertising
background image

SECTION 4 INSTALLING THE

CONVERSION

KIT

(CONTINUED)

Wire Harness Installation (Continued)


A mounting plate is supplied with each hardware kit for
locating the communications portion of the wire harness.
When the communications portion and/or the neutral CT
portion of the wire harness are not to be used, it is
recommended that they be coiled and tied next to the
programmer bracket (Fig. 20).

SECTION 5 INSTALLING THE

PROGRAMMABLE TRIP UNIT


The programmer is attached to the programmer mounting
bracket. The guide pins in the bracket mate with the holes
on either side of the programmer box. The guide pins
provide the necessary alignment for the connector
engagement. The locking lever engages with the pin,
which is assembled to the programmer unit, and secures the
programmer to the mounting bracket.

To Install the Programmer:

Step 1.

Insert the guide pins into the holes and push on the
programmer. This will engage the connectors and release
the locking lever which will move upwards (Fig. 21).

Step 2.

Verify that the locking lever actually engaged with the pin
on the rear of the programmer.

To remove the programmer, pull the locking lever down,
thus releasing the programmer pin. Then, remove the
programmer.

WARNING: BE SURE TO PERFORM THE

13

CONTINUITY TEST DETAILED IN STEP 1 OF
TESTING ON PAGE 17 PRIOR TO ENERGIZING
OR PRIMARY INJECTING THE CONVERTED
BREAKER. FAILURE TO DO SO MAY RESULT IN
DAMAGE TO THE PROGRAMMER UNIT, WIRE
HARNESS, 36-PIN PROGRAMMER CONNECTOR
AND CT’S. FAILURE TO ADHERE TO THESE
INSTRUCTIONS WILL VOID ALL WARRANTIES.

Fig. 19. Caution Label

Fig. 20. Communications and Neutral CT

Wire Leads

Advertising