Fig. 21. Programmer Installation

SECTION 6 FOUR-WIRE

GROUND FAULT OPTION


The ground fault option in all four-wire systems requires an
additional neutral sensor. The neutral sensor is installed in
the neutral bus in the equipment and is connected to the
programmable trip unit through a wiring harness provided.

Step 1.

Mount the neutral sensor on the outgoing neutral lead,
normally in the equipment’s bus or cable compartment
(Figs. 22-24).