Car2012te series rectifier, Data sheet – GE Industrial Solutions CAR2012TE series User Manual

Page 10

Advertising
background image

GE

Data Sheet

CAR2012TE series rectifier

Input: 85Vac to 264Vac; Output: 12 Vdc @ 2000W; 3.3Vdc or 5 Vdc @ 4A

February 9, 2014

©2013 General Electric Company. All rights reserved.

Page 10

The signal will be triggered for any state change whether a

‘warning’ or a ‘fault’, including the following conditions;

VIN under or over voltage

Vout under or over voltage

IOUT over current

Over Temperature

Fan Failure

Communication error

PEC error

Invalid command

Detected internal faults

The power supply will clear the SMBusAlert# signal (release
the signal to its HI state) upon the following events:

Receiving a CLEAR_FAULTS command

Input power and bias power to the processor is recycled


The power supply will clear the SMBusAlert# signal (release
the signal to its HI state) for operational alarms (but not
communications alarms that require a clear_faults signal
from the controller that it received the alert) upon the
following events:

The main output recycled (turned OFF and then ON) via
the Remote_ON/OFF or INTERLOCK signal pins

The main output recycled (turned OFF and then ON) by
the OPERATION command

Standard instruction:

Up to two bytes of data may follow an

instruction depending on the required data content. Analog
data is always transmitted as LSB followed by MSB. PEC is
optional and includes the address and data fields.

1 8 1

8 1

S Slave

address Wr A Command

Code A

8 1 8 1

8

1

1

Low data byte

A High

data

byte A PEC A P

Master to Slave Slave to Master
SMBUS annotations; S – Start , Wr – Write, Sr – re-Start, Rd

– Read,
A – Acknowledge, NA – not-acknowledged, P – Stop

Standard READ:

Up to two bytes of data may follow a READ

request depending on the required data content. Analog
data is always transmitted as LSB followed by MSB. PEC is
mandatory and includes the address and data fields

.

1 7

1

1 8 1

S Slave

address Wr A Command

Code A

1 7 1

1 8

1

Sr Slave

Address Rd A

LSB A

8 1 8

1

1

MSB A PEC No-ack

P

Block communications:

When writing or reading more than

two bytes of data at a time BLOCK instructions for WRITE and
READ commands are used instead of the Standard
Instructions above to write or read any number of bytes
greater than two.

Block write format:

1

7 1

1

8 1

S

Slave address

Wr

A Command

Code A

8 1

8

1

8

1

Byte count = N

A Data

1 A Data

2 A

8 1

8

1

8

1

1

………. A Data

N

≤ 48

A PEC A P

Block read format:

1

7 1

1

8 1

S

Slave address

Wr

A Command

Code A

1 7 1

1

Sr Slave

Address Rd A

8 1

8

1

8

1

Byte count = N

A

Data 1 A Data 2

A

8 1

8

1 8 1 1

………. A

Data N ≤ 48

A

PEC NoAck P

An example of the block_read instruction is the

Read_std_parameters (D0h) command. This ‘manufacturer
specific’ command returns STATUS and ALARM register data,
output voltage, output current, and internal temperature in a
single read string.

1 8 1

8 1

S Slave

address Wr A Command Code

A

1 8 1

8

1

Sr Slave

address Rd A

Byte count = 11

A

8 1 8 1 8 1

Status-2 A Status-1 A Alarm-2 A

8

1 8 1 8 1

Alarm-1 A Voltage LSB

A

Voltage MSB

A

8 1 8 1

Current LSB

A

Current MSB

A

8 1 8 1

8

1

1

Temperature LSB

A

Temperature MSB

A PEC NA P

Linear Data Format

The definition is identical to Part II of the

PMBus Specification. All standard PMBus values, with the
exception of output voltage related functions, are

represented by the linear format described below Output
voltage functions are represented by a 16 bit mantissa. The

value of the exponent for output voltage functions is listed in
the Vout_mode command.