Car2012te series rectifier, Data sheet, Read back descriptions – GE Industrial Solutions CAR2012TE series User Manual

Page 13

Advertising
background image

GE

Data Sheet

CAR2012TE series rectifier

Input: 85Vac to 264Vac; Output: 12 Vdc @ 2000W; 3.3Vdc or 5 Vdc @ 4A

February 9, 2014

©2013 General Electric Company. All rights reserved.

Page 13

STATUS_BYTE (0x78) :

Returns one byte of information with a

summary of the most critical device faults.

Bit

Position

Flag

Default

Value

7 Busy 0
6 OFF 0
5 VOUT

Overvoltage 0

4 IOUT

Overcurrent 0

3 VIN

Undervoltage 0

2 Temperature 0
1

CML (Comm. Memory Fault)

0

0

None of the above

0


STATUS_WORD (0x79):

Returns status_byte as the low byte

and the following high_byte.

Bit

Position

Flag

Default

Value

7

VOUT fault or warning

0

6

IOUT fault or warning

0

5 INPUT 0
4 MFR

SPECIFIC 0

3 nPOWER_GOOD 0
2 FANS 0
1 OTHER 0
0 UNKNOWN 0


STATUS_VOUT (0x7A):

Returns one byte of information of

output voltage related faults.

Bit

Position

Flag

Default

Value

7

VOUT OV Fault

0

6 VOUT_OV_WARNING 0
5 VOUT_UV_WARNING 0
4

VOUT UV Fault

0

3 - 0

Not supported

0

STATUS_IOUT (0x7B):

Returns one byte of information of

output current related faults.

Bit

Position

Flag

Default

Value

7

IOUT OC Fault

0

6 Not

supported 0

5

IOUT OC Warning

0

4- 0

Not supported

0


STATUS_INPUT (0x7C):

Returns one byte of information of

input voltage related faults.

Bit

Position

Flag

Default

Value

7 VIN_OV_Fault 0
6 VIN_OV_Warning 0
5 VIN_UV_

Warning 0

4 VIN_UV_Fault 0

3 - 0

Not supported

0

STATUS_TEMPERATURE (0x7D):

Returns one byte of

information of temperature related faults.

Bit

Position

Flag

Default

Value

7 OT

Fault 0

6 OT

Warning 0

5 - 0

Not supported

0


STATUS_CML
(0x7E):

Returns one byte of information of

communication related faults.

Bit

Position

Flag

Default

Value

7 Invalid/Unsupported

Command 0

6 Invalid/Unsupported

Data 0

5

Packet Error Check Failed

0

4 - 2

Not supported

0

1

Other Communication Fault

0

0 Not

supported 0


STATUS_FAN_1_2 (0x81) :

Returns one byte of information

with a summary of the most critical device faults.

Bit

Position

Flag

Default

Value

7

Fan 1 Fault

0

6

Fan 2 Fault

0

5 - 4

Not supported

0

3

Fan 1 speed overwritten

0

2

Fan 2 speed overwritten

0

1 - 0

Not supported

0

Read back Descriptions

Single parameter read back:

Functions can be read back one

at a time using the read_word_protocol with PEC. A
command is first sent out notifying the slave what function is
to be read back followed by the data transfer.

Analog data is always transmitted LSB followed by MSB. A NA
following the PEC byte signifies that the transmission is
complete and is being terminated by the ‘host’.

1 8 1

8 1

S Slave

address Wr A Command

Code A

1 8 1

Sr Slave

address Rd A

8

1

8

1 8 1 1

LSB A MSB A

PEC NA P


Read_fan_speed 1 & 2 (0x90, 0x91):

Reading the fan speed is

in Linear Mode returning the RPM value of the fan.

Advertising