GE

Data Sheet

CAR2012TE series rectifier

Input: 85Vac to 264Vac; Output: 12 Vdc @ 2000W; 3.3Vdc or 5 Vdc @ 4A

February 9, 2014

©2013 General Electric Company. All rights reserved.

Page 15

Read_Alarm_state (0xD2):

This command returns the two

ALARM register values using the standard ‘read’ format.

Alarm-2

Bit

Position

Flag

Default

Value

7 FAN_Fault 0
6 No_Primary 0
5 Primary_OT 0
4 DC/DC_OT 0
3

Vo lower than BUS

0

2

Thermal sensor filed

0

1 Stby_out_of_limits 0
0 Power_Delivery 0

Power Delivery: The power supply compares its internal
sourced current to the current requested by the current share
pin. If the difference is > 10A, a fault is issued.


Alarm-1

Bit

Position

Flag

Default

Value

7 POWER

LIMIT 0

6 PRIMARY

Fault 0

5 OT_Shutdown 0
4 OT_Warning 0
3 IN

OVERCURRENT 0

2 OV_Shutdown 0
1 VOUT_out_of_limits 0
0 VIN_out_of_limits 0

Over temperature warning: This flag is set approximately
5C prior to the commencement of an over temperature
shutdown.

Read_Fan_speed (0xD3) :

Returns the commanded speed in

percent and the measured speed in RPM. Up to 3 fans are
supported. If a fan does not exist, or if the command is not
supported the unit return 0x00.

1 8 1

8 1

S Slave

address Wr A Command

0xE1 A

1

8

1 8 1

Sr Slave

address Rd A

Byte count = 4

A

8 1

8

1

8

1

8

1

Adjustment %

A

Fan-1 A Fan-2 A Fan-3 A

8 1 1

PEC NA P

Read_input_string (0xD4):

Reads back the input voltage and

input power consumed by the power supply.

1 7 1

1

8

S Slave

address Wr A Command

Code

0xDB

1 1

7

1 1

8

1

A Sr Slave

Address Rd A

Byte Count = 5

A

8 1 8 1

Voltage - LSB

A

Voltage - MSB

A

8 1

8 1

8 1

1

Power - LSB

A Power - MSB A PEC No-ack P

Read_mfr_rev [0xD5]:

A total of 4 bytes are returned. Each

byte is partitioned into high and low nibbles.
Example: FF is read as 16.16

11 is read as 1.1

Series

Hardware Rev

Primary µC

Secondary µC

1 7 1

1 8 1

S Slave

address Wr A Command

Code

0xDD A

1 1

7

1 1

8

1

A Sr Slave

Address Rd A

Byte Count = 4

A

8 1

8 1 8 1

Series A Hardware rev

A

Primary µC

A

8 1

8

1

1

Secondary µC

A PEC No-ack P

For example; the read returns one byte for each device (i.e. 0
x 10102114 ). The sequence is series, hardware rev, DSP, and

I

2

C micro. 0x10 in the first byte indicates series 1.0. The

second number indicates that the hardware rev is 1.0. The

third number 21 for the DSP indicates revision

2.1, and the

number 14 for the i2c

micro indicates revision 1.4.

Read_run_timer (0xD6):

This command reads back the

recorded operational ON state of the power supply in hours.

The operational ON state is accumulated from the time the
power supply is initially programmed at the factory. The

power supply is in the operational ON state both when in
standby and when it delivers main output power.

Recorded capacity is approximately 10 years of operational

state.

1 7 1

1

8

1

S Slave

address Wr A Command

Code

0xDC A

1 7 1

1 8 1

Sr Slave

Address

Rd A

Byte count = 4

A

8 1

8

1 8 1

Time - LSB

A

Time

A

Time - MSB

A

8 1

1

PEC No-ack P