Car2012te series rectifier, Data sheet, Feature specifications (continued) – GE Industrial Solutions CAR2012TE series User Manual

Page 5: Digital interface specifications

Advertising
background image

GE

Data Sheet

CAR2012TE series rectifier

Input: 85Vac to 264Vac; Output: 12 Vdc @ 2000W; 3.3Vdc or 5 Vdc @ 4A

February 9, 2014

©2013 General Electric Company. All rights reserved.

Page 5

Feature Specifications (continued)

Parameter

Symbol

Min

Typ

Max

Unit

SMBAlert# (Interrupt)

(must be pulled up externally to Stndby)

Logic High (No Alert - normal)

I

OH

20 µA

V

OH

0.7V

DD

12 V

DC

Logic Low (Alert is set)

I

OL

4 mA

V

OL

0

0.4 V

DC

Output current monitor (Imon)

Resolution

18

mV/A

Measurement range

I

O

0 167

A

DC

Measurement accuracy, load > 25% of FL, V

O

= 12V

DC

-4

+4

%

Analog output range

V

mon

0 3.3

V

DC

Sourced output current

I

O

5 mA

DC


Digital Interface Specifications

Parameter

Conditions

Symbol

Min

Typ

Max

Unit

PMBus Signal Interface Characteristics
Input Logic High Voltage (CLK, DATA)

V

IH

0.7V

DD

3.6 V

Input Logic Low Voltage (CLK, DATA)

V

IL

0 0.8 V

Input high sourced current (CLK, DATA)

I

IH

0 10 μA

Output Low sink Voltage (CLK, DATA, SMBALERT#)

I

O

=5mA V

OL

0.4 V

Output Low sink current (CLK, DATA, SMBALERT#)

I

OL

5 mA

Output High open drain leakage current (CLK,DATA,
SMBALERT#)

V

O

=3.6V I

OH

0 10 μA

PMBus Operating frequency range

F

PMB

10 400 kHz

Measurement System Characteristics

Clock stretching

t

STRETCH

25

ms

I

OUT

measurement range

Linear mode

I

RNG

0 167 A

I

OUT

measurement accuracy 25°C

I

ACC

-5 +5 %

V

OUT

measurement range

Linear mode

V

OUT(rng)

0 14 V

V

OUT

measurement accuracy

V

OUT(acc)

-5 +5 %

Temp measurement range

Linear mode

Temp

(rng)

0 125

C

Temp measurement accuracy

3

Temp

(acc)

-5 +5 %

I

IN

measurement range

Linear mode

I

IN(rng)

0 18 A

rms

I

IN

measurement accuracy

I

IN(acc)

-5 +5 %

V

IN

measurement range

Linear mode

V

IN(rng)

0 300 V

rms

V

IN

measurement accuracy

V

IN(acc)

-5 +5 %

P

IN

measurement range

Linear mode

P

N(rng)

0 3000 W

P

IN

measurement accuracy

P

IN(acc)

-5 +5 %

Fan Speed measurement range

Linear mode

0 30k RPM

Fan Speed measurement accuracy

-10 10 %

Fan speed control range

Linear mode

0 100 %

3

Temperature accuracy reduces non-linearly with decreasing temperature