Car2012te series rectifier, Data sheet, Environmental specifications – GE Industrial Solutions CAR2012TE series User Manual

Page 6: Emc compliance

Advertising
background image

GE

Data Sheet

CAR2012TE series rectifier

Input: 85Vac to 264Vac; Output: 12 Vdc @ 2000W; 3.3Vdc or 5 Vdc @ 4A

February 9, 2014

©2013 General Electric Company. All rights reserved.

Page 6

Environmental Specifications

Parameter

Min

Typ

Max

Units

Notes

Ambient Temperature

-10

70

°C

Derated above 50C

Storage Temperature

-40

85

°C

Operating Altitude

2250/7382

m/ft

Non-operating Altitude

8200/30k

m / ft

Power Derating with Temperature

2.5

%/°C

50C to 70C

Power Derating with Altitude

2.0

C/301 m

C/1000 ft

Above 2250 m/7382 ft

Acoustic noise

55
45

dbA

Full load
Half load

Over Temperature Protection

125/110

°C

Shutdown / restart

Humidity
Operating
Storage

30
10

95
95

%

Relative humidity, non-condensing

Shock and Vibration

Meet IPC 9592 Class II, Section 5 requirements


EMC Compliance

Parameter

Function

Standard

Level

Criteria

Test

AC input

Conducted
emissions

EN55022, FCC part 15
EN61000-3-2

A*

0.15

30MHz

0 – 2 KHz

Radiated
emissions**

EN55022

A*

30 – 10000MHz

AC input
immunity

Voltage dips

EN61000-4-11

A

-30%, 10ms

B

-60%,

100ms

B

-100%,

5sec

Voltage surge

EN61000-4-5

A

4kV, 1.2/50µs, common mode

A

2kV, 1.2/50µs, differential mode

Fast transients

EN61000-4-4

A

5/50ns, 2kV (common mode)

Enclosure
immunity

Conducted RF
fields

EN61000-4-6

A

130dBµV, 0.15-80MHz, 80% AM

Radiated RF fields

EN61000-4-3

A

10V/m, 80-1000MHz, 80% AM

ENV 50140

A

ESD

EN61000-4-2

B

4kV contact, 8kV air

*

Note: Contact the factory for a recommended external EMI filter to meet Class B emissions

**

Radiated emissions compliance is contingent upon the final system configuration.

Criteria Performance
A

No performance degradation

B

Temporary loss of function or degradation not requiring manual intervention

C

Temporary loss of function or degradation that may require manual intervention

D

Loss of function with possible permanent damage

Advertising