GE

Preliminary Data Sheet

CP2725AC54TE CPL High Efficiency Rectifier

100-120/200-277V

AC

input; Default Outputs: ±54V

DC

@ 2725W, 5V

DC

@ 4W

January 30, 2014

©2013 General Electric Company. All rights reserved.

Page 17

Table 1: FRU_ID

The upper quarter of memory starting from address 6144 shall be reserved for factory ID and factory data.

Memory

Location

Decimal

Memory

Location

(HEX)

Length

(bytes)

Format

Static

Value

Type

Description

Notes/Example

6144d

0x1800

12

ASCII

Fixed

GE-energy - Product ID

CP2725AC54TE

6156d

0x180C

10

ASCII

Fixed

GE-energy – Part Number

123456789x or C123456789

6166d 0x1816 6 ASCII Variable

GE-energy - Hardware revision

x:xxxx controlled by PDI series #

6172d 0x181C 6 ASCII Variable

spare

6178d 0x1822 14 ASCII Variable

GE-energy - Serial_No

01KZ51018193xx
01 …. Year of manufacture - 2001

KZ … factory, in this case Matamoros

51 .. week of manufacture
______018193xx serial # mfg choice

6192d 0x1830 40 ASCII Variable

GE- Manufacturing location

“Matamoros, Tamps, Mexico”

6232d 0x1858 8 ASCII Fixed

spare

6240d 0x1860 2 HEX Fixed

spare

6242d 0x1862 158 ASCII Fixed

Customer Information

These fields are reserved for use by the
customer.

6400d

0x1900

5

HEX

Fixed

M, B, & R for voltage read

M & B are 2 bytes each sent as MSB and then
LSB. R is one byte. These are stored as two’s
complement.

See the section on Direct Mode Constants
Stored in the EEPROM for the constants stored
in these fields

6405d

0x1905

5

HEX

Fixed

M, B, & R for current read

6410d

0x190A

5

HEX

Fixed

M, B, & R temp read

6415d 0x190F 5 HEX Fixed spare
6420d

0x1914

5

HEX

Fixed

M, B, & R for voltage set

6425d

0x1919

5

HEX

Fixed

M, B, & R for input voltage read

6430d 0x191E 1 HEX Variable

Validation

CHKSUM

6431d

9x191F

5

HEX

Fixed

M, B, & R for input power read

6436d

0x1924

5

HEX

Fixed

M, B, & R for fan percent adjust

6441d

0x1929

5

HEX

Fixed

M, B, & R for fan RPM read

6446d

0 x 192E

5

HEX

Fixed

M, B, & R for converter input
voltage read

Notes:

CHkSUM is a CRC-8 calculation from location 0x1800 to location 0x19FF without including serial number and checksum locations. chksum_value =
0xFF - (mask of SUM with 0x0000ff) write chksum_value byte to location 0x191E.

Table 2: Alarm and LED state summary

Power Supply LED State

Monitoring Signals

Condition

AC OK

Green

DC OK

Green

Service

Amber

Fault

Red

Fault OTW PFW

Module

Present

OK 1

1

0

0

HI HI HI LO

Thermal Alarm (5C before shutdown)

1

1

1

0

HI LO HI LO

Thermal Shutdown

1

0

1

1

LO LO LO LO

Defective Fan

1

0

0

1

LO HI LO LO

Blown AC Fuse in Unit

1

0

0

1

LO HI LO LO

AC Present but not within limits

Blinks

0

0

0

HI HI LO LO

AC not present

1

0 0 0 0

HI HI LO LO

Boost Stage Failure

1

0

0

1

LO HI LO LO

Over Voltage Latched Shutdown

1

0

0

1

LO HI LO LO

Over Current

1

Blinks

0

0

HI HI LO LO

Non-catastrophic Internal Failure

2

1

1

0

1

LO HI HI

LO

Missing Module

HI

Standby (remote)

1

0

0

0

HI HI LO LO

Service Request (PMBus mode)

1

1

Blinks

0

HI HI HI LO

Communications Fault (RS485 mode)

1

1

0

Blinks

HI HI HI LO

1

This signal is correct if the rectifier is back biased from other rectifiers in the shelf .

2

Any detectable fault condition that does not cause a shutting down. For example, ORing FET failure, boost section out of regulation, etc.

3

Signal transition from HI to LO is output load dependent