Data sheet, Input; default outputs: ±54v, Electrical specifications (continued) – GE Industrial Solutions CP2725AC54TE User Manual

Page 3

Advertising
background image

GE

Data Sheet

CP2725AC54TE CPL High Efficiency Rectifier

100-120/200-277V

AC

input; Default Outputs: ±54V

DC

@ 2725W, 5V

DC

@ 4W

January 30, 2014

©2013 General Electric Company. All rights reserved.

Page 3

Electrical Specifications (continued)

54V

DC

MAIN OUTPUT

Parameter

Symbol

Min

Typ

Max

Unit

Output Power @ low line input 100 – 120V

AC

@ high line input 200 – 277V

AC

@ nominal 277Vac and T

amb

> 45C

W

1200
2725
2000

W

DC

Default Set point

V

OUT

54

V

DC

Overall regulation (load, temperature, aging) 0 - 45C LOAD > 2.5A
> 45C

-1
-2

+1
+2

%

Output Voltage Set Range - analog margining
- Set either by I

2

C or RS485

44
42

58
58

V

DC

Output Current - @ 1200W (100 – 120Vac), 54V/52V
@ 2725W (200 – 240V

AC

), 54V/52V

@ 2000W ( > 277V

AC

@ Tamb > 45C), 54V/52V

I

Out

1
1
1

25/23

50.5/52.4

37/38.4

A

DC

Current Share ( > 50% FL)

-5 5

%FL

Proportional Current Share between different rectifiers ( > 50% FL)

<7

%FL

Output Ripple ( 20MHz bandwidth, load > 1A)
RMS (5Hz to 20MHz)
Peak-to-Peak (5Hz to 20MHz)
Psophometric Noise

V

OUT

100

300

4

9

5

mV

rms

mV

p-p

mV

rms

External Bulk Load Capacitance

C

OUT

0

5,000

F

Turn-On (monotonic turn-ON from 30 – 100% of Vnom above 5C)
Delay
Rise Time – PMBus mode

Rise Time - RS-485 mode

6

Output Overshoot


T

V

OUT

5

100

5




2

s

ms

s

%

Load Step Response ( I

O,START

> 2.5A )

I
V, V

AC

 285

AC

V, V

AC

≥ 285

AC

Response Time

I

OUT

V

OUT

V

OUT

T


2.0
3.2

2

50



%FL

V

DC

V

DC

ms

Overload - Power limit @ high line down to 52V

DC

Power limit @ low line down to 52V

DC

High line current limit if V

out

> 41.5V

DC

High line current limit if V

out

< 41.5V

DC

Low line current limit
Output shutdown (commences as voltage decays below this level)

P

OUT

P

OUT

I

OUT

V

OUT

2725
1200

53

36
26



39

W

DC

W

DC

A

DC

A

DC

A

DC

V

DC

System power up

Upon insertion the power supply will delay an overload shutdown
for 20 seconds allowing for the insertion and startup of multiple
modules within a system.

Overvoltage - 200ms delayed shutdown
Immediate shutdown

V

OUT

> 65

< 65

V

DC

Latched shutdown

Three restart attempts are implemented within a 1 minute window

prior to a latched shutdown.

Over-temperature warning (prior to commencement of shutdown)

Shutdown (below the max device rating being protected)
Restart attempt Hysteresis (below shutdown level)

T

5

20
10

C

Isolation Output-Chassis (Standard, non-POE compliant)
Output-Chassis/Signals (POE compliant per IEEE802.3)

V

500

2250

V

DC

V

DC

4

500mVp-p max above 280V

AC

input

or above 56Vdc output;

5

Complies with ANSI TI.523-2001 section 4.9.2 emissions max limit of 20mV flat unweighted wideband noise limits

6

Below -5°C, the rise time is approximately 5 minutes to protect the bulk capacitors.