Data sheet, Front view rear view, Input; default outputs: ±54v – GE Industrial Solutions CP2725AC54TE User Manual

Page 19: Mechanical outline, Output connector, Top view

Advertising
background image

GE

Data Sheet

CP2725AC54TE CPL High Efficiency Rectifier

100-120/200-277V

AC

input; Default Outputs: ±54V

DC

@ 2725W, 5V

DC

@ 4W

January 30, 2014

©2013 General Electric Company. All rights reserved.

Page 19

Mechanical Outline

Dimensions

Front Panel LEDs

Analog Mode

I

2

C Mode

RS485 Mode

ON: Input ok
Blinking: Input out of limits

ON: Output ok
Blinking: Overload

ON: Over-temperature Warning

ON: Over-temperature Warning
Blinking: Service

ON: Over-temperature Warning

ON: Fault

Blinking: Not communicating

Output Connector

Mating Connector: right angle PWB mate – all pins: AMP 6450572-1, right angle PWB mate except pass-thru input power: AMP 6450378-1

P1

A6

P7

A1

351.2 mm

(13.85 in)

101.6mm

(4.00 in)

Top View

41.4mm

(1.63 in)

Front View

Rear View

!

6

5

4

3

2

1

A

SCL_0

MOD_PRES

PFW

LOGIC_GRD

RS_485+

UNIT_ADDR

B

SCL_1

OTW

Alert#_0

Alert#_1

RS_485-

8V_INT

C

SDA_0

Margin

Enable

Reset

Ishare

Protocol

D

SDA_1

Fault

5VA

Power_Cap

ON/OFF

SHELF_ADDR

Note: Connector is viewed from the rear positioned inside the rectifier
Signal pins columns 1 and 2 are referenced to V_OUT (–)

Earth

( + )

( + )

P4

V_OUT

Manufacturer part numbers: FCI 51939-568

Last to make-first to break shortest pin
First make-last to break longest pin implemented in the mating connector

SIGNAL

P5

V_OUT

Signal pins columns 3 through 6 are referenced to Logic GRD

P6

V_OUT

( - )

P7

(Neutral)

P3

INPUT POWER

OUTPUT POWER

EARTH

P1

LINE-1

(HOT)

(GND)

( - )

V_OUT

P2

LINE-2

ON: Fault

Advertising