Data sheet, Input; default outputs: ±54v, Environmental specifications – GE Industrial Solutions CP2725AC54TE User Manual

Page 6

Advertising
background image

GE

Data Sheet

CP2725AC54TE CPL High Efficiency Rectifier

100-120/200-277V

AC

input; Default Outputs: ±54V

DC

@ 2725W, 5V

DC

@ 4W

January 30, 2014

©2013 General Electric Company. All rights reserved.

Page 6

Environmental Specifications

Parameter

Min

Typ

Max

Units

Notes

Ambient Temperature

-40

12

55

13

°C

Air inlet from sea level to 5,000 feet.

Storage Temperature

-40

85

°C

Operating Altitude

1524/5000

m / ft

Non-operating Altitude

8200/30k

m / ft

Power Derating with Temperature

2.0

%/°C

55°C to 75C

14

Power Derating with Altitude

2.0

C/305 m

C/1000 ft

Above 1524/5000 m/ft; 3962/13000 m/ft
max

Acoustic noise

55

dbA

Full load

Over Temperature Protection

125/110

°C

Shutdown / restart [internally measured

points]

Humidity
Operating

Storage

5
5

95
95

%
%


Relative humidity, non-condensing

Shock and Vibration acceleration

6

Grms

NEBS GR-63-CORE, Level 3, 20 -2000Hz, min
30 minutes

Earthquake Rating

4

Zone

NEBS GR-63-CORE, all floors, Seismic Zone 4

Designed and tested to meet NEBS
specifications.


EMC

Parameter

Criteria

Standard

Level

Test

AC input

Conducted emissions

EN55022, FCC Docket 20780 part 15, subpart J
EN61000-3-2
Meets Telcordia GR1089-CORE by a 3dB margin

A 0.15

30MHz

0 – 2 KHz

Radiated emissions

EN55022

A

30 – 10000MHz

AC Input
Immunity

Line sags and

interruptions

EN61000-4-11

B

-30%, 10ms

B -60%,

100ms

B -100%,

5sec

Output will stay above 40V

DC

@ full load

25% line sag for 2 seconds

Sag must be higher than 80Vrms.

1 cycle interruption

Lightning surge

EN61000-4-5, Level 4, 1.2/50µs – error free

A

4kV, common mode

A 2kV,

differential

mode

ANSI C62.41 - damage free

A3

6kV, common & differential

Fast transients

EN61000-4-4, Level 3

B

5/50ns, 2kV (common mode)

Enclosure
immunity

Conducted RF fields

EN61000-4-6, Level 3

A

130dBµV, 0.15-80MHz, 80% AM

Radiated RF fields

EN61000-4-3, Level 3

A

10V/m, 80-1000MHz, 80% AM

ENV

50140

A

ESD

EN61000-4-2, Level 3

B

6kV contact, 8kV air


12

Designed to start and work at an ambient as low as -40°C, but may not meet operational limits until above -5°C

13

Output power is derated to 2kW for temperatures higher than 45C and input voltages higher than 285V

AC

.

14

The maximum operational ambient is reduced in Europe in order to meet certain power cord maximum ratings of 70C. The maximum

operational ambient where 70C rated power cords are utilized is reduced to 60C until testing demonstrates that a higher level is acceptable.

Advertising