Data sheet, Input; default outputs: ±54v, Table 3: signal definitions – GE Industrial Solutions CP2725AC54TE User Manual

Page 18

Advertising
background image

GE

Data Sheet

CP2725AC54TE CPL High Efficiency Rectifier

100-120/200-277V

AC

input; Default Outputs: ±54V

DC

@ 2725W, 5V

DC

@ 4W

January 30, 2014

©2013 General Electric Company. All rights reserved.

Page 18

Table 3: Signal Definitions

All hardware alarm signals (Fault, PFW, OTW, Power Capacity) are open drain FETs. These signals need to be pulled HI to either 3.3V or 5V.
Maximum sink current 5mA. An active LO signal (< 0.4V

DC

) state. All signals are referenced to Logic_GRD unless otherwise stated.

Function

Label

Type

Description

Output Enable

Enable

Input

If shorted to Logic_GRD main output is ON in Analog or PMBus mode.

Power Fail Warning

PFW

Output An open drain FET; Changes to LO  5msec before the output decays below 40V

DC

.

I

2

C Interrupt

Alert#_0/Alert#_1

Output This signal is pulled to 3.3V via a 10kΩ resistor. Active LO.

Rectifier Fault

Fault

Output An open drain FET; normally HI, changes to LO.

Module Present

MOD_PRES

Output Short pin, see Status and Control description for further information on this signal.

ON/OFF

ON/OFF

Input

Short pin, controls main output during hot-insertion and extraction. Ref: Vout ( - )

Protocol select

Protocol

Input

Selects operational mode. Ref: Vout ( - ). No-connect PMBus, 10kΩ - RS485

Margining

Margin

Input

Changes the default set point of the main output.

Over-Temperature Warning OTW

Output Open drain FET; normally HI, changes to LO 5°C prior to thermal shutdown.

Power Capacity

POWER_CAP

Output Open drain FET; HI indicates 2725W operation and LO indicates 1200W operation.

Rectifier address

Unit_addr

Input

Voltage level addressing of Rectifiers within a single shelf. Ref: Vout ( - ).

Shelf Address

Shelf_addr

Input

Voltage level addressing of Rectifiers within multiple shelves. Ref: Vout ( - ).

Back bias

8V_INT

Bi-direct Used to back bias the DSP from operating Rectifiers. Ref: Vout ( - ).

Mux Reset

Reset

Input

Resets the internal PCA9541 multiplexer

Standby power

5VA

Output 5V at 0.75A provided for external use

Current Share

Ishare

Bi-direct A single wire active-current-share interconnect between modules Ref: Vout ( - ).

I

2

C Line 0

SCL_0

Input

PMBus line 0.

I

2

C Line 0

SDA_0

Bi-direct

PMBus line 0.

I

2

C Line 1

SCL_1

Input

PMBus line 1.

I

2

C Line 1

SDA_1

Bi-direct

PMBus line 1.

SMBALERT# Line 0

ALERT#_0

Output PMBus line 0 interrupt

SMBALERT# Line 1

ALERT#_1

Output PMBus line 1 interrupt

RS485 Line

RS_485+

Bi-direct RS485 line +

RS485 Line

RS_485-

Bi-direct RS485 line -