Data sheet, Input; default outputs: ±54v, Digital interface specifications – GE Industrial Solutions CP2725AC54TE User Manual

Page 5

Advertising
background image

GE

Data Sheet

CP2725AC54TE CPL High Efficiency Rectifier

100-120/200-277V

AC

input; Default Outputs: ±54V

DC

@ 2725W, 5V

DC

@ 4W

January 30, 2014

©2013 General Electric Company. All rights reserved.

Page 5

Feature Specifications (continued)

Parameter

Symbol

Min

Typ

Max

Unit

Power Capacity Logic HI

V

0.7V

DD

12 V

DC

Logic LO

V

0

0.4 V

DC

Reset Logic HI

V

0.7V

DD

12

V

DC

Logic LO

V

0

0.4 V

DC

Protocol select Logic HI - Analog/PMBus™ mode

V

IH

2.7

3.5

V

DC

Logic – intermediate – RS485 mode

V

II

1.0 2.65

V

DC

Logic LO – DSP reprogram mode

V

IL

0

0.4 V

DC

Digital Interface Specifications

Parameter

Conditions

Symbol

Min

Typ

Max

Unit

PMBus Signal Interface Characteristics
Input Logic High Voltage (CLK, DATA)

V

1.5

3.6

V

DC

Input Logic Low Voltage (CLK, DATA)

V

0

0.8

V

DC

Input high sourced current (CLK, DATA)

I

0

10

μA

Output Low sink Voltage (CLK, DATA, SMBALERT#)

I

OUT

=3.5mA V 0.4 V

DC

Output Low sink current (CLK, DATA, SMBALERT#)

I

3.5

mA

Output High open drain leakage current (CLK,DATA,

SMBALERT#)

V

OUT

=3.6V I

0 10 μA

PMBus Operating frequency range

Slave Mode

FPMB

10

400

kHz

Measurement System Characteristics
Clock stretching

T

stretch

25 ms

I

OUT

measurement range

Direct

I

rng

0 50

8

A

DC

I

OUT

measurement accuracy 25°C

I

out(acc)

-2.5 +2.5

%

of

FL

V

OUT

measurement range

Direct

V

out(rng)

0

70 V

DC

V

OUT

measurement accuracy

9

V

out(acc)

-1 +1 %

Temp measurement range

Direct

Temp

(rng)

0

150

C

Temp measurement accuracy

10

Temp

(acc)

-5 +5 %

V

IN

measurement range

Direct

V

in(rng)

0 320 V

AC

V

IN

measurement accuracy

V

in(acc)

-1.5 +1.5 %

P

IN

measurement range

Direct

P

in(rng)

0 3000 W

in

P

IN

measurement accuracy

11

P

in(acc)

-3.5 +3.5 %

Fan Speed measurement range

Direct

0

30k

RPM

Fan Speed measurement accuracy

-10

10

%

Fan speed control range

Direct

0

100

%

Device Addressing

Unit address [reference: V

OUT

( - )]

Module 1

V

unitadr

2.3 2.477 3.3 V

DC

Module 2

V

unitadr

1.6 1.925 2.2 V

DC

Module 3

V

unitadr

0.9 1.243 1.5 V

DC

Module 4

V

unitadr

0 0.654 0.8 V

DC

Shelf address [reference: V

OUT

( - )]

Shelf 1

V

shelfadr

3.0 3.3 3.45 V

DC

Shelf 2

V

shelfadr

2.7 2.86 2.97 V

DC

Shelf 3

V

shelfadr

2.18 2.4 2.56 V

DC

Shelf 4

V

shelfadr

1.73 1.96 2.14 V

DC

Shelf 5

V

shelfadr

1.29 1.50 1.70 V

DC

Shelf 6

V

shelfadr

0.84 1.10 1.25 V

DC

Shelf 7

V

shelfadr

0.30 0.60 0.80 V

DC

Shelf 8

V

shelfadr

0 0.01 0.25 V

DC

8

Load levels higher than 50A will be read as 50A.

9

Above 2.5A of load current

10

Temperature accuracy reduces non-linearly with decreasing temperature

11

Below 100W input power measurement accuracy reduces significantly

Advertising