Adjusting the Flux Shifter

With the breaker in the CLOSED position, the gap
between the adjustment screw and the trip paddle
should be

1

/

16

inch, as shown in Figure 15. For safety,

OPEN the breaker to adjust the screw with a

1

/

4

-inch

wrench.

WARNING:

Be extremely careful when working on a

closed breaker.

Do not

reach into the mechanism

while adjusting the flux shifter.

12

Optional Test

– The flux shifter may be tested by

closing the breaker and applying a 9 Vdc power
source to the flux shifter leads (the red wire is posi-
tive). The breaker should trip.

Figure 15. Flux shifter adjustment.

Connecting the Trip Unit Wiring Harness

1. Join the four-pin connector on the trip unit har-

ness to the four-pin connector on the flux shifter.

2. Connect the harness leads to the screw terminals

on each CT, as shown in Figure 16. The black wire

(tap) connects to the left terminal and the white

wire (common) to the right terminal.

3. Use the wire ties provided to tie the harness back

against the frame. The harness should be tied to

the holes in the fiber barriers at each CT. Ensure

that the wiring will not interfere with any moving

parts.

Figure 16. Wiring harness installation.