SECTION 3. DISASSEMBLING THE
BREAKER

GE Type AK-1 breakers need not have their front and
back frames separated for installation of the
conversion kit. The procedure is to remove the old
electromechanical trip units, then install the kit.
First, remove the breaker from its compartment and
place it on a clean, well-lighted workbench in an
upright position, so that both the front and back are
easily accessible.

Component Removal

1. Remove and save the load terminal primary dis-

connect fingers on all draw-out breakers. They

are held in place with a

1

/

4

-20 bolt, as shown in

Figure 1.

2. Remove and discard the two screws on each side

of the EC trip units, shown in Figure 2, that hold

the covers in place.

3. Remove and discard the Philips-head screw

above each EC trip unit. It may be necessary to

remove the left and right trip paddles. The trip

paddles may be discarded.

4. Remove and discard the two

5

/

16

-inch Allen-head

bolts holding the trip unit coils to the breaker

frame.

5. Remove and discard the three electromechanical

trip units. The disassembled breaker is shown in

Figure 4.

Figure 1. Draw-out primary disconnect fingers.

Figure 2. EC trip unit removal.

Figure 3. Removing the trip unit coil connections.

Figure 4. Disassembled AK-1-25 breaker.

6