Af-60 lp ™ micro drive – GE Industrial Solutions AF-60 LP Micro Drive Installation Guide User Manual

Page 11

Advertising
background image

[Off/Reset]:

Stops the motor (off). If in alarm mode the alarm will be reset.

[Auto]:

The frequency converter is controlled either via control terminals or serial communication.

[Potentiometer]:

The potentiometer works in two ways depending on the mode in which the frequency converter is running.

In Auto Mode the potentiometer acts as an extra programmable analog input.
In Hand Mode the potentiometer controls local reference.

Arrows [

] and [

] toggles between the choices in each menu.

The display indicates the status mode with a small arrow above “Status”.

The Quick Menu gives easy access to the most frequently used parameters.

1.

To enter the Quick Menu, press [MENU] key until indicator in display is placed above Quick Menu.

2.

Use [

] [

] to select either QM1 or QM2, then press [OK].

3.

Use [

] [

] to browse through the parameters in the Quick Menu.

4.

Press [OK] to select a parameter.

5.

Use [

] [

] to change the value of a parameter setting.

6.

Press [OK] to accept the change.

7.

To exit, press either [Back] twice to enter Status, or press [Menu] once to enter Main Menu.

No

Name

Range

Default

Function

1-20 Motor Power [kW]/[HP] [0.09kW/0.12HP -30kW/40HP] Unit dependent Enter motor power from nameplate data
1-22 Motor Voltage

[50 - 999V]

230/400

Enter motor voltage from nameplate data

1-23 Motor Frequency

[20 - 400 Hz]

50

Enter motor frequency form nameplate data

1-24 Motor Current

[0.01 - 100.00 A]

Unit dependent Enter motor current from nameplate data

1-25 Motor nominal speed

[100 - 9999 RPM]

Unit dependent Enter motor nominal speed from nameplate data

1-29 Auto Tune

[0] = off
[2] = Enable Auto Tune

[0] = off

Use Auto Tune to optimize motor performance.
1. Stop Drive
2. Choose [2]
3. "Hand "

3-02 Minimum reference

[-4999 - 4999]

0

Enter value for minimum reference

3-03 Maximum reference

[-4999 - 4999]

50.00

Enter value for maximum reference

3-41 Accel time 1

[0.05 - 3600s]

3.00 (10.00

1)

)

Accel time from 0 to rated motor frequency par. 1-23

3-42 Decel time 1

[0.05 - 3600s]

3.00 (10.00

1)

)

Decel time form rated motor frequency par. 1-23 to 0

1)

M4 and M5 only

Table 1.4: Basic Settings Quick Menu 1

The Main Menu gives access to all parameters.

1.

To enter the Main Menu, press [MENU] key until indicator in display is placed above Main Menu.

2.

Use [

] [

] to browse through the parameter groups.

3.

Press [OK] to select a parameter group.

4.

Use [

] [

] to browse through the parameters in the specific group.

5.

Press [OK] to select the parameter.

6.

Use [

] [

] to set/change the parameter value.

7.

Press [OK] to accept the value.

8.

To exit, press either [Back] twice to enter Quick Menu, or press [Menu] once to enter Status.

AF-60 LP

™ Micro Drive

10

DEH-41264A

1