1.1.11 Electrical Installation in General

NB!

All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper conductors required, (60-75

° C) recom-

mended.

Details of terminal tightening torques.

Power

(kW)

Torque

(Nm)

Unit Size

1 x 200-240 V

3 x 200-240 V

3 x 380-480 V

Line

Motor

DC connection/Brake

Control Terminals

Earth

Relay

M1

0.18 - 0.75

0.25 - 0.75

0.37 - 0.75

1.4

0.7

Spade

1)

0.15

3

0.5

M2

1.5

1.5

1.5 - 2.2

1.4

0.7

Spade

1)

0.15

3

0.5

M3

2.2

2.2 - 3.7

3.0 - 7.5

1.4

0.7

Spade

1)

0.15

3

0.5

M4

11.0-15.0

1.3

1.3

1.3

0.15

3

0.5

M5

18.5-22.0

1.3

1.3

1.3

0.15

3

0.5

1)

Spade connectors (6.3 mm Faston plugs)

Table 1.2: Tightening of terminals.

1.1.12 Fuses

Branch circuit protection:
In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuited and
overcurrent protected according to national/international regulations.

Short circuit protection:
GE Drive is suitable for a circuit capable of supplying a maximum of 100,000 A

rms

(symmetrical), 480 V maximum.

Overcurrent protection:
Provide overload protection to avoid overheating of the cables in the installation. Overcurrent protection must always be carried out according to national
regulations.

Non UL compliance:
If UL/cUL is not to be complied with, GE recommends using the fuses mentioned in the below table, which will ensure compliance with EN50178/IEC61800-5-1:
In case of malfunction, not following the fuse recommendation may result in damage to the frequency converter.

AF-60 LP

™ Micro Drive

4

DEH-41264A