Af-60 lp ™ micro drive – GE Industrial Solutions AF-60 LP Micro Drive Installation Guide User Manual

Page 16

Advertising
background image

No. Description

Warning Alarm

Trip

Lock

Error Cause of Problem

2

Live zero error

X

X

Signal on terminal 53 or 60 is less than 50% of value set in par. 6-10,
6-12 and 6-22.

4

Mains phase loss

1)

X

X

X

Missing phase on supply side, or too high voltage imbalance. Check
supply voltage.

7

DC over voltage

1)

X

X

Intermediate circuit voltage exceeds limit.

8

DC under voltage

1)

X

X

Intermediate circuit voltage drops below “voltage warning low” limit.

9

Driveoverloaded

X

X

More than 100% load for too long.

10

Motor Electronic Overload over
temperature

X

X

Motor is too hot due to more than 100% load for too long.

11

Motor thermistor over temperature

X

X

Thermistor or thermistor connection is disconnected.

12

Torque limit

X

Torque exceeds value set in either par. 4-16 or 4-17.

13

Over Current

X

X

X

Drive current limit is exceeded.

14

Earth fault

X

X

Discharge from output phases to ground.

16

Short Circuit

X

X

Short-circuit in motor or on motor terminals.

17

Control word timeout

X

X

No communication to frequency converter.

25

Brake resistor short-circuited

X

X

Brake resistor is short-circuited, thus brake function is disconnected.

27

Brake chopper short-circuited

X

X

Brake transistor is short-circuited, thus brake function is disconnec-
ted.

28

Brake check

X

Brake resistor is not connected/working

29

Power board over temp

X

X

X

Heat-sink cut-out temperature has been reached.

30

Motor phase U missing

X

X

Motor phase U is missing. Check the phase.

31

Motor phase V missing

X

X

Motor phase V is missing. Check the phase.

32

Motor phase W missing

X

X

Motor phase W is missing. Check the phase.

38

Internal fault

X

X

Contact local GE supplier.

44

Earth fault

X

X

Discharge from output phases to ground.

47

Control Voltage Fault

X

X

24 V DC may be overloaded.

51

Auto Tune check U

nom

and I

nom

X

Wrong setting for motor voltage and/or motor current.

52

Auto Tune low I

nom

X

Motor current is too low. Check settings.

59

Current limit

X

Drive overload.

63

Mechanical

Brake

Low

X

Actual

motor

current

has not exceeded “release brake” current within

“start delay” time window.

80

Drive restored to Factory Settings

X

All parameter settings are restored to factory default settings.

84

The connection between drive and
Keypad is lost

X

No communication between Keypad and frequency converter

85

Button disabled

X

See parameter group 0-4* Keypad

86

Copy fail

X

An error occurred while copying from frequency converter to
Keypad or vice versa.

87

Keypad data invalid

X

Occurs when copying from Keypad if the Keypad contains erroneous
data - or if no data was uploaded to the Keypad.

88

Keypad data not compatible

X

Occurs when copying from Keypad if data are moved between fre-
quency converters with major differences in software versions.

89

Parameter read only

X

Occurs when trying to write to a read-only parameter.

90

Parameter database busy

X

Keypad and RS485 connection are trying to update parameters si-
multaneously.

91

Parameter value is not valid in this
mode

X

Occurs when trying to write an illegal value to a parameter.

92

Parameter value exceeds the min/
max limits

X

Occurs when trying to set a value outside the range.

nw
run

Not While RUNning

X

Parameter can only be changed when the motor is stopped.

Err. A wrong password was entered

X

Occurs when using a wrong password for changing a password-pro-
tected parameter.

1)

These faults may be caused by mains distortions. Installing GE Line Filter may rectify this problem.

Table 1.5: Warnings and AlarmsCode list

AF-60 LP

™ Micro Drive

DEH-41264A

15

1