1.1.7 Disposal Instruction

Equipment containing electrical components must not be disposed of together with domestic waste.
It must be separately collected with electrical and electronic waste according to local and currently valid legislation.

1.1.8 Before Commencing Repair Work

1.

Disconnect AF-60 LP

™ Micro Drive from mains (and external DC supply, if present.)

2.

Wait for 4 minutes (M1, M2 and M3) and 15 minutes (M4 and M5) for discharge of the DC-link.

3.

Disconnect DC bus terminals and brake terminals (if present)

4.

Remove motor cable

1.1.9 Side-by-Side Installation

The frequency converter can be mounted side-by-side for IP 20 rating units and requires 100 mm clearance above and below for cooling. Please refer to the
specifications near the end of this document for details on environmental ratings of the frequency converter.

1.1.10 Mechanical Dimensions

A template for drilling can be found on the flap of the packaging.

Illustration 1.1: Mechanical dimensions.

Power (kW)

Height (mm)

Width (mm)

Depth

1)

(mm) Max. Weight

Unit
Size

1 X 200-240 V 3 X 200 -240 V 3 X 380-480 V

A

A (incl. decoupling plate)

a

B

b

C

Kg

M1

0.18 - 0.75

0.25 - 0.75

0.37 - 0.75

150

205

140.4

70

55

148

1.1

M2

1.5

1.5

1.5 - 2.2

176

230

166.4

75

59

168

1.6

M3

2.2

2.2 -3.7

3.0 - 7.5

239

294

226

90

69

194

3.0

M4

11.0-15.0

292

347.5

272.4

125

97

241

6.0

M5

18.5-22.0

335

387.5

315

165

140

248

9.5

1)

For Keypad with potentiometer, please add 7.6 mm.

Table 1.1: Mechanical Dimensions

AF-60 LP

™ Micro Drive

DEH-41264A

3

1