Af-60 lp ™ micro drive – GE Industrial Solutions AF-60 LP Micro Drive Installation Guide User Manual

Page 21

Advertising
background image

Surroundings:

Enclosure

IP 20

Enclosure kit available

IP 21, TYPE 1

Vibration test

1.0 g

Max. relative humidity

5% - 95%(IEC 60721-3-3; Class 3K3 (non-condensing) during operation

Aggressive environment (IEC 60721-3-3), coated

class 3C3

Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature

Max. 40 °C

Derating for high ambient temperature, see section on special conditions

Minimum ambient temperature during full-scale operation

0 °C

Minimum ambient temperature at reduced performance

- 10 °C

Temperature during storage/transport

-25 - +65/70 °C

Maximum altitude above sea level without derating

1000 m

Maximum altitude above sea level with derating

3000 m

Derating for high altitude, see section on special conditions

Safety standards

EN/IEC 61800-5-1, UL 508C

EMC standards, Emission

EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3

EMC standards, Immunity

EN 61800-3, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3,

EN 61000-4-4, EN 61000-4-5, EN 61000-4-6

See section on special conditions

AF-60 LP