Max. voltage

20 V

Current level

0/4 to 20 mA (scaleable)

Input resistance, R

i

approx. 200 Ω

Max. current

30 mA

Analog output:
Number of programmable analog outputs

1

Terminal number

42

Current range at analog output

0/4 - 20 mA

Max. load to common at analog output

500 Ω

Max. voltage at analog output

17 V

Accuracy on analog output

Max. error: 0.8 % of full scale

Resolution on analog output

8 bit

Control card, RS-485 serial communication:

Terminal number

68 (P,TX+, RX+), 69 (N,TX-, RX-)

Terminal number 61

Common for terminals 68 and 69

Control card, 24 V DC output:

Terminal number

12

Max. load (M1 and M2)

160 mA

Max. load (M3)

30 mA

Max. load (M4 and M5)

200 mA

Relay output:

Programmable relay output

1

Relay 01 Terminal number

01-03 (break), 01-02(make)

Max. terminal load (AC-1)

1)

on 01-02 (NO) (Resistive load)

250 V AC, 2 A

Max. terminal load (AC-15)

1)

on 01-02 (NO) (Inductive load @ cosφ 0.4)

250 V AC, 0.2 A

Max. terminal load (DC-1)

1)

on 01-02 (NO) (Resistive load)

30 V DC, 2 A

Max. terminal load (DC-13)

1)

on 01-02 (NO) (Inductive load)

24 V DC, 0.1A

Max. terminal load (AC-1)

1)

on 01-03 (NC) (Resistive load)

250 V AC, 2 A

Max. terminal load (AC-15)

1)

on 01-03 (NC) (Inductive load @ cosφ 0.4)

250 V AC, 0.2A

Max. terminal load (DC-1)

1)

on 01-03 (NC) (Resistive load)

30 V DC, 2 A

Min. terminal load on 01-03 (NC), 01-02 (NO)

24 V DC 10 mA, 24 V AC 20 mA

Environment according to EN 60664-1

overvoltage category III/pollution degree 2

1) IEC 60947 part 4 and 5

Control card, 10 V DC output:

Terminal number

50

Output voltage

10.5 V ±0.5 V

Max. load

25 mA

NB!
All inputs, outputs, circuits, DC supplies and relay contacts are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.