Car2512te front-end, Preliminary data sheet, Input: 90v – GE Industrial Solutions CAR2512TE Front-End User Manual

Page 13: Output: 12 v, Standby @ 15w, Alarm table, Outline drawing

Advertising
background image

GE

Preliminary Data Sheet

CAR2512TE Front-End

Input: 90V

AC

to 264V

AC

; Output: 12 V

DC

@ 2500W; 3.3/5V

DC

standby @ 15W

February 7, 2014

©2013 General Electric Company. All rights reserved.

Page 13

Alarm Table

Test Condition

LED Indicator

Monitoring Signals

LED1

AC

Tri-Color LED2

DC / FLT

FAULT

DC_OK

INPUT_OK

TEMP_OK

1 Normal

Operation

Green

Green

High High High High

2

Low or NO INPUT

Off

Red

Low Low Low High

3 OVP

Green

Red

Low Low High High

4 Over

Current

Green

Red

Low Low High High

5

Temp Alarm Warning

Green

Orange

High

High High Low

6 Fault

Over

Temp

Green

Red

Low Low High Low

7 Remote

ON/OFF

Green

Red

Low Low High High

Notes: Test condition #2 had 2 modules plug in. One module is running and the other one is with no AC.

Outline Drawing


airflow

15.817 ±.020

15.375 ±.020

COVER

CHASSIS

0.330

Advertising