Car2512te front-end, Preliminary data sheet, Input: 90v – GE Industrial Solutions CAR2512TE Front-End User Manual

Page 9: Output: 12 v, Standby @ 15w, Pmbus, Commands

Advertising
background image

GE

Preliminary Data Sheet

CAR2512TE Front-End

Input: 90V

AC

to 264V

AC

; Output: 12 V

DC

@ 2500W; 3.3/5V

DC

standby @ 15W

February 7, 2014

©2013 General Electric Company. All rights reserved.

Page 9

SMBAlert#

:

The µC driven SMBAlert# signal informs the

‘master/host’ controller that either a STATE or ALARM change
has occurred. Normally this signal is HI. The signal will change

to its LO level if the power supply has changed states and the
signal will be latched LO until the power supply receives a
‘clear’ instruction as outlined below. If the alarm state is still

present after the ‘clear_faults’ command has been received,
then the signal will revert back into its LO state again and will
latch until a subsequent ‘clear_faults’ signal is received from

the host controller.

The signal will be triggered for any state change, including the
following conditions;

VIN under or over voltage

Vout under or over voltage

IOUT over current

Over Temperature warning or fault

Fan Failure

Communication error

PEC error

Invalid command

Detected internal faults

The power supply will clear the SMBusAlert# signal (release the
signal to its HI state) upon the following events:

Receiving a CLEAR_FAULTS command

The main output recycled (turned OFF and then ON) via
the REMOTE ON/OFF signal pin

The main output recycled (turned OFF and then ON) by the
OPERATION command

Read back delay:

The power supply issues the SMBAlert #

notification as soon as the first state change occurred.

During

an event a number of different states can be transitioned to
before the final event occurs. If a read back is implemented
rapidly by the host a successive SMBAlert# could be triggered

by the transitioning state of the power supply. In order to avoid
successive SMBAlert# s and read back and also to avoid
reading a transitioning state, it is prudent to wait more than 2

seconds after the receipt of an SMBAlert# before executing a
read back. This delay will ensure that only the final state of the

power supply is captured.

Successive read backs:

Successive read backs to the power

supply should not be attempted at intervals faster than every

one second. This time interval is sufficient for the internal
processors to update their data base so that successive reads
provide fresh data.

Invalid commands or data:

The power supply notifies the

MASTER if a non-supported command has been sent or invalid
data has been received. Notification is implemented by setting

the appropriate STATUS and ALARM registers and setting the
SMBAlert# flag.
If a non-supported read is requested the power supply will

return all 0x00h.

PMBus

TM

Commands

Standard instruction:

Up to two bytes of data may follow an

instruction depending on the required data content. Analog
data is always transmitted as LSB followed by MSB. PEC is
optional and includes the address and data fields.

1

8 1

8 1

S Slave address

Wr

A Command

Code A

8 1 8 1

8

1

1

Low data byte

A

High data byte

A PEC A P

Master to Slave Slave to Master
SMBUS annotations; S – Start , Wr – Write, Sr – re-Start, Rd –
Read,
A – Acknowledge, NA – not-acknowledged, P – Stop

Standard READ:

Up to two bytes of data may follow a READ

request depending on the required data content. Analog data
is always transmitted as LSB followed by MSB. PEC is
mandatory and includes the address and data fields

.

PEC is

optional and includes the address and data fields.

1

7 1

1

8 1

S

Slave address

Wr

A Command

Code A

1 7 1

1 8

1

Sr Slave

Address Rd A

LSB A

8 1 8

1

1

MSB A PEC No-ack

P

Block communications:

When writing or reading more than

two bytes of data at a time, BLOCK instructions for WRITE and
READ commands must be used instead of the Standard
Instructions

Block write format:

1

7 1

1

8 1

S

Slave address

Wr

A Command

Code A

8

1 8 1 8

1

Byte count = N

A Data

1 A Data

2 A

8 1 8 1 8 1

1

………. A Data

48 A PEC A P

Block read format:

1

7 1

1

8 1

S

Slave address

Wr

A Command

Code A

1 7 1

1

Sr Slave

Address Rd A

8 1

8

1

8

1

Byte count = N

A

Data 1

A Data 2

A

8 1 8 1 8 1 1

………. A

Data 48

A

PEC NoAck P