Car2512te front-end, Preliminary data sheet, Input: 90v – GE Industrial Solutions CAR2512TE Front-End User Manual

Page 14: Output: 12 v, Standby @ 15w, Connector pin assignments

Advertising
background image

GE

Preliminary Data Sheet

CAR2512TE Front-End

Input: 90V

AC

to 264V

AC

; Output: 12 V

DC

@ 2500W; 3.3/5V

DC

standby @ 15W

February 7, 2014

©2013 General Electric Company. All rights reserved.

Page 14

Connector Pin Assignments

Input Connector:

IEC320, C20; mating connector: IEC320, C19 type

Output Connector:

Tyco P/N 6600122-7 or equivalent

Mating connector: Primary Source:

FCI berg P/N 51915-176LF

Secondary Source: Tyco P/N 6450171-5

Pin

Function

Pin

Function

Pin

Function

Pin

Function

A1 V

STDBY

B1

Fault

C1

IShare

D1

VProg

A2

PS Present

B2

Current Monitor (Imon)

C2

V

STDBY

D2

OVP Test Point

6

A3 V

STDBY

Return

B3

Interlock

C3

Over_Temp_Warning

D3

Remote ON/OFF

A4 n/c B4

V

STDBY

Return

C4

I

2

C Address (A0)

D4

DC_OK

A5

Remote Sense (+)

B5

SDA (I

2

C bus)

C5

I

2

C Address (A1)

D5

AC_OK

A6

Remote Sense (-)

B6

SCL (I

2

C bus)

C6

I

2

C Address (A2)

D6

SMBAlert

P1 – P6

Output Return

P7– P12

+12V

OUT

6

For factory use