Car2512te front-end, Preliminary data sheet, Input: 90v – GE Industrial Solutions CAR2512TE Front-End User Manual

Page 6: Output: 12 v, Standby @ 15w, Environmental specifications, Emc compliance

Advertising
background image

GE

Preliminary Data Sheet

CAR2512TE Front-End

Input: 90V

AC

to 264V

AC

; Output: 12 V

DC

@ 2500W; 3.3/5V

DC

standby @ 15W

February 7, 2014

©2013 General Electric Company. All rights reserved.

Page 6

Environmental Specifications

Parameter

Min

Typ

Max

Units

Notes

Ambient Temperature

-10 70

5

°C

Derated above 50C

Storage Temperature

-40

85

°C

Operating Altitude

2250/7382

m/ft

Meet CCC at 5000m

Non-operating Altitude

8200/30k

m / ft

Power Derating with Temperature

2.5

%/°C

50C to 70C(60C max where TUV/VDE is required)

Power Derating with Altitude

2.0

C/301 m

C/1000 ft

Above 2250 m/7382 ft

Acoustic noise

55

dbA

Full load

Over Temperature Protection

125/110

°C

Shutdown / restart

Humidity
Operating
Storage

30
10

95
95

% Relative

humidity,

non-condensing

Shock and Vibration acceleration

2.4

Grms

Meet IPC-9592B Class II




EMC Compliance

Parameter

Criteria

Standard

Level

Test

AC input

Conducted emissions

EN55022, FCC Docket 20780 part 15, subpart J
EN61000-3-2( line harmonics)

A 0.15

30MHz

0 – 2 KHz

Radiated emissions**

EN55022

A

30M – 1GHz

AC input
immunity

Voltage dips

EN61000-4-11

B

-30%, 10ms

B -60%,

100ms

B -100%,

5sec

Voltage surge

EN61000-4-5

A

4kV, 1.2/50µs, common mode

A

2kV, 1.2/50µs, differential mode

Fast transients

EN61000-4-4

B

5/50ns, 2kV (common mode)

Enclosure
immunity

Conducted RF fields

EN61000-4-6

A

130dBµV, 0.15-80MHz, 80% AM

Radiated RF fields

EN61000-4-3

A

10V/m, 80-1000MHz, 80% AM

ENV 50140

A

ESD

EN61000-4-2

3

6kV contact, 8kV air

5

60C max where TUV/VDE is required

Advertising