Evolution Series E9000 Installation & Maintenance Guide

Size 0 and 1 (Ambient Comp.)

Size 2 (Standard)

Size 2 (Ambient Comp.)

Size 3 (Standard and Ambient Comp.)

Motor Full-

Heater

TEC &

Mag-Break

Load Amps

Number

TECL

Trip Setting

3-Ph, 3 Heater

CR 123

Rating

Rec.

Max.

17.8-18.4

F233B

30

1

5

18.5-21.1

F243B

30

1

6

21.2-22.1

F270B

30

2

7

22.2-26.0

F300B

30

3

7

26.1-28.0

F327B

50

LO

4

28.1-31.3

F357B

50

LO

4

31.4-33.3

F395B

50

1

5

33.4-34.3

F430B

50

1

6

34.4-40.9

F487B

50

1

6

41.0-43.4

F567B

50

2

8

43.5-44.7

F567B

100

LO

3

44.8-51.0

F614B

100

LO

3

51.1-52.0

F658B

100

1

4

52.1-55.4

F719B

100

1

4

Motor Full-

Heater

TEC &

Mag-Break

Load Amps

Number

TECL

Trip Setting

3-Ph, 3 Heater

CR 123

Rating

Rec.

Max.

9.04-9.61

C104B

15

2

5

9.62-10.5

C113B

15

2

6

10.6-11.6

C125B

15

3

7

11.7-12.5

C137B

15

3

8

11.7-12.5

C137B

30

LO

2

12.6-13.0

C151B

15

4

9

12.6-13.6

C151B

30

LO

3

13.7-16.7

C163B

30

1

3

16.8-17.9

C180B

30

1

5

18.0-18.7

C198B

30

2

5

18.8-20.4

C214B

30

2

6

20.5-22.7

C228B

30

2

7

22.8-24.7

C250B

30

3

8

22.8-24.7

C250B

50

LO

2

24.8-26.0

C273B

30

4

9

24.8-26.3

C273B

50

LO

4

26.4-29.5

C303B

50

LO

4

29.6-32.5

C330B

50

1

4

32.6-36.7

C366B

50

2

6

36.8-41.9

C400B

50

2

7

42.0-43.2

C440B

50

3

9

43.3-43.4

C460B

50

3

9

Motor Full-

Heater

TEC &

Mag-Break

Load Amps

Number

TECL

Trip Setting

3-Ph, 3 Heater

CR 123

Rating

Rec.

Max.

8.81-9.27

C104B

15

2

5

9.28-9.99

C113B

15

2

6

10.0-11.1

C125B

15

3

6

11.2-12.1

C137B

15

3

7

11.2-12.1

C137B

30

LO

2

12.2-13.0

C151B

15

4

8

12.2-13.0

C151B

30

LO

2

13.1-15.5

C163B

30

1

3

15.6-16.8

C180B

30

1

4

16.9-18.0

C198B

30

2

5

18.1-19.7

C214B

30

2

5

19.8-21.6

C228B

30

2

6

21.7-23.9

C250B

30

3

7

21.7-23.9

C250B

50

LO

2

24.0-25.5

C273B

30

3

8

24.0-25.5

C273B

50

LO

3

25.6-26.0

C303B

30

3

9

25.6-28.2

C303B

50

LO

3

28.3-31.6

C330B

50

1

4

31.7-34.7

C366B

50

2

5

34.8-37.8

C400B

50

2

6

37.9-40.6

C440B

50

3

7

40.7-43.4

C460B

50

3

8

Motor Full-

Heater

TEC &

Mag-Break

Load Amps

Number

TECL

Trip Setting

3-Ph, 3 Heater

CR 123

Rating

Rec.

Max.

.66-.76

C087A

3

LO

LO

.77-.84

C097A

3

LO

LO

.85-.93

C109A

3

LO

1

.94-1.04

C118A

3

LO

1

1.05-1.15

C131A

3

LO

2

1.16-1.27

C148A

3

LO

2

1.28-1.39

C163A

3

LO

3

1.40-1.55

C184A

3

LO

4

1.56-1.73

C196A

3

1

4

1.74-1.89

C220A

3

1

5

1.90-2.05

C239A

3

2

6

2.06-2.28

C268A

3

2

7

2.29-2.47

C301A

3

3

8

2.29-2.47

C301A

7

LO

1

2.48-2.79

C326A

7

LO

2

2.80-3.31

C356A

7

LO

3

3.32-3.70

C379A

7

LO

4

3.71-4.06

C419A

7

1

5

4.07-4.47

C466A

7

1

5

4.48-4.95

C526A

7

2

6

4.96-5.49

C592A

7

2

7

4.96-5.49

C592A

15

LO

1

5.50-5.91

C630A

7

3

8

5.50-5.91

C630A

15

LO

2

5.92-6.47

C695A

15

LO

2

6.48-7.20

C778A

15

LO

3

7.21-8.22

C867A

15

LO

3

8.23-8.72

C955A

15

1

4

8.73-9.67

C104B

15

1

5

9.68-10.4

C113B

15

1

6

10.5-11.0

C125B

15

2

7

11.1-12.4

C137B

15

2

7

11.1-12.4

C137B

30

LO

2

12.5-13.2

C151B

30

LO

2

13.3-15.4

C163B

30

LO

3

15.5-17.1

C180B

30

LO

4

Size 1

17.2-18.1

C198B

30

1

5

18.2-20.0

C214B

30

1

5

20.1-21.5

C228B

30

2

6

21.6-22.5

C250B

30

2

7

22.6-23.9

C273B

30

2

8

22.6-23.9

C273B

50

LO

2

24.0-26.0

C303B

30

3

8

24.0-26.0

C303B

50

LO

3

26.1-27.0

C330B

50

LO

4

Advertising