This publication provides guidelines for installation and
maintenance of Evolution Motor Control Centers, as
shown in Figure 1. The information provided does not
cover all details or variations in this product offering,
nor does it address all possible contingencies to be
met in connection with installation, operation, or main-
tenance. Should further information be desired, contact
GE Field Service Administration:
Call GE–RESOLve
1-888-437-3765

Refer to the GE requisition number found on the front
of the equipment when calling for assistance.

For additional information, including safety considera-
tions for personnel working on this product, see NEMA
Standard Publication No. ICS 2.3, Instructions on the
Handling, Installation, Operation, and Maintenance of
Motor Control Centers
.

Figure 1. Evolution Series three-section lineup.

General Description –
Vertical Section Enclosures

Each Evolution MCC vertical section is assembled with
two full-side sheets having openings near the top and
bottom for lateral busing and wiring between sections.
Multiple sections are joined together at the factory in
three-section (maximum) shipping splits. Each shipping
split is provided with continuous floor sills and a lifting
angle. Floor sills and lifting angles are field removable.
Each shipping split includes a continuous non-removable
main horizontal bus. Main bus splice bars are provided
within each shipping split for field connecting main
busses. Refer to motor control center outline drawings
furnished by the General Electric Company for location of
shipping splits within each motor control center lineup.

Vertical sections are normally provided with a top (12"
high) horizontal wireway and a bottom (6" high) horizontal
wireway. Each vertical section is also provided with a
vertical (4" wide) wireway. Hinged doors are provided
over horizontal and vertical wireways. (These doors can
be removed by extracting the hinge pins inside the doors.)

Secure

Open

Because of the great variety of motor controller
assemblies and components provided within industrial
motor control centers and to satisfy floor-space limitations
at installation sites, a large variety of vertical section
dimensions are provided, as follows:

• Section Height:

90”, 78”, 66” etc.

• Section Width:

20”, 24”, 30” etc.

• Section Depth:

13”, 20”, 22” or deeper
for large assemblies.

Refer to motor control center drawings
furnished by GE before performing any
field-installation work.

To open the external doors, rotate the
latches 90° counter-clockwise until the
screwdriver slots are vertical.

Disconnect equipment from all electrical
services before performing any installation
or maintenance work.