Size 3 (Ambient Comp.)

Size 4 (Standard)

Size 4 (Ambient Comp.)

➀ See maximum fuse and short-circuit rating table on page 29.

Size 5 – 300:15CT (Standard and Ambient Comp.)

Electronic Overload Table for Fusible Controllers
Tripping current is 120% of Dial setting. Motors with 1.15-1.25 serv-
ice factor, set dial to motor FLA Motors with 1.0 service factor, set
dial to 0.9 motor FLA.

300:15 CT’s

800:5 CT’s

Additional motor overload protection required for
MM200 abd MM300 relay applications with FLA
less than 6A.

NEMA Size FLA Range in Amps Catalog Number

Max. Fuse in Amps

1

0.8 to 1.59

CR324CXD

Class R 30

Class J 60

1

1.6 to 3.19

CR324CXE

1

3.2 to 6.49

CR324CXF

1

6.5 to 12.8

CR324CXG

1

13 to 27

CR324CXH

2

13 to 25.6

CR324DXG

60

100

2

26 to 49.9

CR324DXH

2

50 to 100

CR324DXJ

3

17 to 34.9

CR324FXK

100

200

3

35 to 64.9

CR324FXL

3

65 to 90

CR324FXM

4

17 to 34.9

CR324FXK

200

400

4

35 to 64.9

CR324FXL

4

65 to 135

CR324FXM

5

32 to 64.0

CR324GXN

400

600

5

65 to 129.9

CR324GXP

5

130 to 270

CR324GXQ

6

130 to 259.9

CR324HXS

600

Class L 1200

6

260 to 540

CR324HXT

Motor Full-

Heater

Maximum

Load Amps

Number

Fuse

3-Ph., 3-Heater

CR123

Rating

109-118

C592A

600

119-128

C630A

600

129-138

C695A

600

139-155

C778A

600

156-168

C867A

600

169-184

C955A

600

185-200

C104B

600

201-221

C113B

600

222-237

C125B

600

238-262

C137B

600

263-270

C151B

600

Motor Full-

Heater

Maximum

Load Amps

Number

Fuse

3-Ph., 3-Heater

CR123

Rating

28.8-32.0

F357B

110

32.1-34.2

F395B

125

34.3-36.7

F430B

125

36.8-43.9

F487B

150

44.0-46.6

F567B

175

46.7-52.6

F614B

175

52.7-55.6

F658B

200

55.7-58.7

F719B

225

58.8-67.1

F772B

225

67.2-70.6

F848B

250

70.7-76.3

F914B

275

76.4-88.7

F104C

300

88.8-93.4

F114C

350

93.5-105

F118C

350

106-114

F133C

400

115-128

F149C

400

129-131

F161C

400

132-135

F174C

400

Motor Full-

Heater

Maximum

Load Amps

Number

Fuse

3-Ph., 3-Heater

CR123

Rating

27.1-32.2

F357B

110

32.3-34.0

F395B

125

34.1-36.8

F430B

125

36.9-44.6

F487B

150

44.7-48.4

F567B

175

48.5-53.9

F614B

175

54.0-57.4

F658B

200

57.5-60.0

F719B

225

60.1-69.5

F772B

225

69.6-71.7

F848B

250

71.8-79.9

F914B

275

80.0-92.3

F104C

300

92.4-97.0

F114C

350

97.1-108

F118C

400

109-118

F133C

400

119-131

F149C

400

132-135

F161C

400

Motor Full-

Heater

Maximum

Load Amps

Number

Fuse

3-Ph., 3-Heater

CR123

Rating

17.8-18.4

F233B

70

18.5-21.1

F243B

80

21.2-22.1

F270B

80

22.2-26.1

F300B

90

26.2-28.0

F327B

100

28.1-31.3

F357B

110

31.4-33.3

F395B

125

33.4-34.3

F430B

125

34.4-40.9

F487B

150

41.0-44.7

F567B

150

44.8-51.0

F614B

175

51.1-52.0

F658B

200

52.1-55.4

F719B

200

55.5-63.3

F772B

200

63.4-66.1

F848B

200

66.2-73.5

F914B

200

73.6-82.2

F104C

200

82.3-90.0

F114C

200

Advertising