GE Industrial Solutions Evolution Series E9000 User Manual

Page 30

Advertising
background image

29

Evolution Series E9000 Installation & Maintenance Guide

Size 4 (Standard)

Size 4 (Ambient Comp.)

Size 4 (Standard)

Size 4 (Ambient Comp.)

Motor Full-

Heater

SF

Mag-Break

Load Amps

Number

Rating

Trip Setting

3-Ph, 3 Heater

CR123

Plug

Rec.

Max.

28.8-32.0

F357B

70

2

4

32.1-34.2

F395B

70

3

4

34.3-36.7

F430B

70

3

5

36.8-43.8

F487B

70

3

5

43.9-46.6

F567B

70

3

5

46.7-52.6

F614B

100

2

4

52.7-55.6

F658B

100

2

4

55.7-58.7

F719B

100

2

5

58.8-67.1

F772B

150

LO

4

67.2-70.6

F848B

150

LO

4

70.7-76.3

F914B

150

2

4

76.4-88.7

F104C

200

LO

4

88.8-93.4

F114C

200

LO

4

93.5-105.0

F118C

200

LO

5

106.0-114.0

F133C

200

2

6

115.0-128.0

F149C

200

2

6

129.0-130.0

F161C

200

2

6

Motor Full-

Heater

SF

Mag-Break

Load Amps

Number

Rating

Trip Setting

3-Ph, 3 Heater

CR123

Plug

Rec.

Max.

28.8-32.0

F357B

70

2

4

32.1-34.2

F395B

70

2

4

34.3-36.7

F430B

70

2

5

36.8-43.9

F487B

70

2

5

44.0-46.6

F567B

70

3

5

46.7-52.6

F614B

100

2

4

52.7-55.6

F658B

100

2

4

55.7-58.7

F719B

100

2

5

58.8-67.1

F772B

150

LO

4

67.2-70.6

F848B

150

LO

4

70.7-76.3

F914B

150

2

4

76.4-88.7

F104C

200

LO

4

88.8-93.4

F114C

200

LO

4

93.5-102.0

F118C

200

LO

5

103.0-110.0

F133C

200

2

6

111.0-122.0

F149C

200

2

6

123.0-131.0

F161C

200

2

6

Motor Full-

Heater

SE

Mag-Break

Load Amps

Number

Rating

Trip Setting

3-Ph, 3 Heater

CR123

Plug

Rec.

Max.

28.8-32.0

F357B

50

3

5

32.1-34.2

F395B

50

3

5

34.3-36.7

F430B

70

2

5

36.8-43.9

F487B

70

3

5

44.0-46.6

F567B

70

3

5

46.7-52.6

F614B

100

2

4

52.7-55.6

F658B

100

2

5

55.7-58.7

F719B

100

2

5

58.8-67.1

F772B

100

3

5

67.2-70.6

F848B

100

3

6

70.7-76.3

F914B

150

2

4

76.4-88.7

F104C

150

2

5

88.8-93.4

F114C

150

3

5

93.5-102.0

F118C

150

3

5

103.0-110.0

F133C

150

3

5

111.0-122.0

F149C

150

4

6

123.0-131.0

F161C

150

4

6

Motor Full-

Heater

SE

Mag-Break

Load Amps

Number

Rating

Trip Setting

3-Ph, 3 Heater

CR123

Plug

Rec.

Max.

28.8-32.0

F357B

50

3

5

32.1-34.2

F395B

50

3

5

34.3-36.7

F430B

70

2

5

36.8-43.8

F487B

70

3

5

43.9-46.6

F567B

70

3

5

46.7-52.6

F614B

100

2

4

52.7-55.6

F658B

100

2

5

55.7-58.7

F719B

100

2

5

58.8-67.1

F772B

100

3

5

67.2-70.6

F848B

100

3

6

70.7-76.3

F914B

150

2

4

76.4-88.7

F104C

150

2

5

88.8-93.4

F114C

150

3

5

93.5-105.0

F118C

150

3

5

106.0-114.0

F133C

150

3

5

115.0-128.0

F149C

150

4

6

129.0-130.0

F161C

150

4