Ge energy, 2a dlynx, Non-isolated dc-dc power modules – GE Industrial Solutions 2A DLynx User Manual

Page 14: Datasheet, Feature descriptions

Advertising
background image

GE Energy

Datasheet

2A DLynx

TM

: Non-Isolated DC-DC Power Modules

3Vdc –14Vdc input; 0.6Vdc to 5.5Vdc output; 2A Output Current

June 24, 2013

©2012 General Electric Company. All rights reserved.

Page 14

Feature Descriptions

Remote Enable

The 12V DLynx

TM

2A power modules feature an On/Off pin for

remote On/Off operation. Two On/Off logic options are
available. In the Positive Logic On/Off option, (device code
suffix “4” – see Ordering Information), the module turns ON

during a logic High on the On/Off pin and turns OFF during a
logic Low. With the Negative Logic On/Off option, (no device
code suffix, see Ordering Information), the module turns OFF

during logic High and ON during logic Low. The On/Off signal is
always referenced to ground. For either On/Off logic option,

leaving the On/Off pin disconnected will turn the module ON
when input voltage is present.

For positive logic modules, the circuit configuration for using

the On/Off pin is shown in Figure 43. Contact GE Energy
regarding availability of positive logic module

Q1

VIN+

GND

+

PWM Enable

ON/OFF

V

ON/OFF

_

MODULE

I

Rpullup

ON/OFF

10K

Q2

10K

50K

50K

Q3

10K

10K

Figure 43. Circuit configuration for using positive On/Off

logic.

For negative logic On/Off modules, the circuit configuration is
shown in Fig. 44.

Q1

ON/OFF

VIN+

GND

+

PWM Enable

V

ON/OFF

_

MODULE

I

Rpullup

ON/OFF

10K

Q2

10K


Figure 44. Circuit configuration for using negative On/Off
logic.


Overcurrent Protection

To provide protection in a fault (output overload)
condition, the unit is equipped with internal
current-limiting circuitry and can endure current limiting

continuously. At the point of current-limit inception, the
unit enters hiccup mode. The unit operates normally
once the output current is brought back into its specified

range.

Overtemperature Protection

To provide protection in a fault condition, the unit is
equipped with a thermal shutdown circuit. The unit will
shutdown if the overtemperature threshold of 140

o

C is

exceeded at the thermal reference point T

ref

. The

thermal shutdown is not intended as a guarantee that
the unit will survive temperatures beyond its rating.

Once the unit goes into thermal shutdown it will then
wait to cool before attempting to restart.

Input Undervoltage Lockout

At input voltages below the input undervoltage lockout
limit, the module operation is disabled. The module will
begin to operate at an input voltage above the
undervoltage lockout turn-on threshold.

Output Voltage Programming

The output voltage of the 12V DLynx

TM

2A modules can

be programmed to any voltage from 0.6dc to 5.5Vdc by
connecting a resistor between the Trim and GND pins of

the module. Certain restrictions apply on the output
voltage set point depending on the input voltage. These
are shown in the Output Voltage vs. Input Voltage Set

Point Area plot in Fig. 45. The Lower Limit curve shows
that for output voltages of 2.4V and higher, the input

voltage needs to be larger than the minimum of 3V.

0

2

4

6

8

10

12

14

16

0.5

1

1.5

2

2.5

3

3.5

4

4.5

5

5.5

6

Output Voltage (V)

In

p

u

t V

o

lt

ag

e

(v

)

Figure 45. Output Voltage vs. Input Voltage Set Point
Area plot showing limits where the output voltage can

be set for different input voltages.

Without an external resistor between Trim and GND pins,
the output of the module will be 0.6Vdc. To calculate the

value of the trim resistor, Rtrim for a desired output
voltage, use the following equation:

Advertising