6KBU300

—————— TECHNICAL DATA ——————

3

3

3.2. HARDWARE SPECIFICATIONS

3.2.1. Power required

The supply of the braking unit is directly obtained by the DC Link and the maximum consumption is 15W.

3.2.2. Internal fuses

Denomination

Protection for

Fuses

F1

Switching input supply

4A 500V slow 6 x 32 mm

F2

+24V supply (terminals 1 and 2)

315mA 250V slow 5 x 20 mm

Master output command (terminals 5 and 6)

F3

Supply of the internal fan (+24V)

1A 250V slow 5 x 20 mm

bu0015

The fuse F2 for the +24V supply (terminals 1 and 2) and Master output command (terminals 5 and 6) is mounted
on the front panel.

Replacement vendor sources:

Fuse 1

- Omega (Europe) GF632240

Fuse 2

- Omega (Europe) ST520131

- Littlefuse 218315

Fuse 3

- Omega (Europe) ST520210

- Littlefuse 218001

3.2.3. Signalling LEDs

Denomination

Colour

Function

24 V

green

It shows presence of the power supply

MASTER

yellow

The braking unit is set as master

BR

yellow

The braking unit is active (braking)

OK

green

OK relay status (closed = OK)

AL

red

It shows the alarm condition

bu0020

3.2.4. Terminal strip

The power terminal strip is composed by the following terminals:

Terminals

Function

I/Q

Volt. max.

Curr. max.

C

Connection to the intermediate circuit of the
inverter

I

770Vdc

I peak

D

Connection to the intermediate circuit of the
inverter

I

770Vdc

I peak

CR

Connection to the braking resistor

Q

745V dc

I peak

BR

Connection to the braking resistor

Q

745V dc

I peak

PE

Ground connection

bu0025