Hardware specifications 3.2.1. power required, Internal fuses, Signalling leds – GE Industrial Solutions 6KBU300 Braking Unit User Manual
Page 13: Terminal strip
6KBU300
—————— TECHNICAL DATA ——————
3
3
3.2. HARDWARE SPECIFICATIONS
3.2.1. Power required
The supply of the braking unit is directly obtained by the DC Link and the maximum consumption is 15W.
3.2.2. Internal fuses
Denomination
Protection for
Fuses
F1
Switching input supply
4A 500V slow 6 x 32 mm
F2
+24V supply (terminals 1 and 2)
315mA 250V slow 5 x 20 mm
Master output command (terminals 5 and 6)
F3
Supply of the internal fan (+24V)
1A 250V slow 5 x 20 mm
bu0015
The fuse F2 for the +24V supply (terminals 1 and 2) and Master output command (terminals 5 and 6) is mounted
on the front panel.
Replacement vendor sources:
Fuse 1
- Omega (Europe) GF632240
Fuse 2
- Omega (Europe) ST520131
- Littlefuse 218315
Fuse 3
- Omega (Europe) ST520210
- Littlefuse 218001
3.2.3. Signalling LEDs
Denomination
Colour
Function
24 V
green
It shows presence of the power supply
MASTER
yellow
The braking unit is set as master
BR
yellow
The braking unit is active (braking)
OK
green
OK relay status (closed = OK)
AL
red
It shows the alarm condition
bu0020
3.2.4. Terminal strip
The power terminal strip is composed by the following terminals:
Terminals
Function
I/Q
Volt. max.
Curr. max.
C
Connection to the intermediate circuit of the
inverter
I
770Vdc
I peak
D
Connection to the intermediate circuit of the
inverter
I
770Vdc
I peak
CR
Connection to the braking resistor
Q
745V dc
I peak
BR
Connection to the braking resistor
Q
745V dc
I peak
PE
Ground connection
–
–
–
bu0025