Dip switches description, Selection of the intervention threshold, Parallel connection of the unit – GE Industrial Solutions 6KBU300 Braking Unit User Manual
Page 14: Simplified dimensioning of the resistance, Dip switches description 5
GEI-100350A
—————— TECHNICAL DATA ——————
3
4
Regulation board terminal strips:
Terminals
Name
Function
I/Q
Volt. max.
Curr. max.
1
+24V
Supply for commands TIM-RESET
Q
24V
200mA
2
0V 24V
0V potential of the +24V supply
–
–
3
TIM
Connection for the thermal contact of
resistor protection
I
15...30V
3.2...6.4 mA
4
RESET
Remote Reset of alarm condition
I
15...30V
3.2...6.4 mA
5
MCMD
Slave unit command (Master output)
Q
24V ± 5%
30 mA
6
0V 24V
0V potential of MCMD command
–
–
7
SIN
Slave unit input command
I
8...30V
16 mA
8
SIN
Slave unit input command
I
8...30V
16 mA
9
SOUT
Cascade connection of Slave units
Q
8...30V
16 mA
10
SOUT
Cascade connection of Slave units
Q
8...30V
16 mA
75
OK
OK relay dry contact (closed = OK)
Q
250Vca
1 A
76
OK
OK relay dry contact (closed = OK)
Q
250Vca
1 A
bu0030
Maximum cable sizes for power terminals C,D,CR,BR
Braking Unit type
Maximum Permissible Cable Cross-Section
[mm
2
]
flexible
multi-core
6KBU300-20
10
10
12
6KBU300-50
16
16
10
6KBU300-85
35
35
2
bu0031
AWG
Maximum cable sizes of the regulation section terminals
Terminals
Maximum Permissible Cable Cross-Section
[mm
2
]
flexible
multi-core
1 ... 76
0.35 ... 1.5
0.35 ... 1.5
22 ... 16
bu0032
AWG