—————— DIMENSIONING... AND CORRESPONDING... ——————

4

5

To calculate the value of the costant power (or rated) of the braking resistor using this graphic, it will be possible
to apply the following formula:

continuative power R =

BR

regenerated power

overload factor

f013

Considering having to brake a 30KW motor with overload of 150%, the regenerated power will be at maximum
45KW.

Supposing a braking time of 5 seconds (overload time for the resistor) and 1 break minute, the graphic provides an
overload factor of 3,9, so the rated power of the resistor will be:

= 11.5 kW

45000

3.9

f014

N

OTE

:

The use of the normalized resistors reported at chapter 6 it is strongly reccomended